beautypg.com

EVCO EPK4BHQ1AH Hardware manual User Manual

Page 20

background image

EVCO S.p.A.

c-pro 3 NODE kilo+ | Hardware manual ver. 1.0 | Code 114CP3NKPE104

page 20 of 55

B1/-

RS-485 MODBUS master/slave port negative pole

A2/+

RS-485 MODBUS slave port positive pole

B2/-

RS-485 MODBUS slave port negative pole

The following table shows the Function codes supported by the device, provided that it works in commander mode with a MODBUS

communication protocol.

FUNCT.

CODE

MEANING

FC 01

read coils

FC 02

read discrete inputs

FC 03

read multiple registers

FC 04

read input registers

FC 05

write single coil

FC 06

write single register

FC 08

diagnostic

FC 15

write multiple coils

FC 16

write multiple registers

FC 23

read write multiple registers (maximum 10 registers)

The RS-485 MODBUS slave and RS-485 MODBUS master/slave ports can be used for one of the following operations:

-

device configuration (through the Parameters Manager set-up software system)

-

device supervision (through the CloudEvolution system monitoring and supervision (via Web) system)

-

MODBUS master function use with regard to other slave devices.

The CAN CANBUS port can be used to connect the device to the I/O expansions and remote user interfaces of the c-pro 3 range

The maximum number of devices that can be comprised in the CAN network (32) depends on the BUS load; the BUS load, in turn,

depends on the baud rate of the CANBUS communication and on the type of device (for instance, a CAN network can comprise 1

programmable controller with 4 I/O expansions and 4 remote user interfaces with a baud rate of 500,000 baud).

USB

USB port

Through the USB port it is possible to carry out one of the following actions:

-

upload and download of application software (through the UNI-PRO 3 development environment or USB flash drive)

-

application software debug (through the UNI-PRO 3 development environment)

-

device configuration (through the Parameters Manager set-up software system or a USB flash drive)

-

file transfer (through the UNI-PRO 3 development environment)

-

data logging (through a USB flash drive).

Please see paragraph 6 "CONFIGURATION" for the settings of the USB port.