EVCO S.p.A.

c-pro 3 NODE kilo+ | Hardware manual ver. 1.0 | Code 114CP3NKPE104

page 16 of 55

ANALOG INPUTS

Analog inputs

Please see paragraph 6 "CONFIGURATION" for the settings of the analog inputs.

PART

MEANING

GND

analog inputs ground

AI1

analog input 1 settable by way of the PTC, NTC, Pt 1000 probes configuration parameter, transducers 0-20 mA, 4-20

mA, 0-5 V ratiometric or 0-10 V

AI2

analog input 2 settable by way of the PTC, NTC, Pt 1000 probes configuration parameter, transducers 0-20 mA,

4-20 mA, 0-5 V ratiometric o 0-10 V

AI3

analog input 3 settable by way of the PTC, NTC, Pt 1000 probes configuration parameter, transducers 0-20 mA,

4-20 mA, 0-5 V ratiometric o 0-10 V

AI4

analog input 4, settable by way of the PTC, NTC, Pt 1000 probes configuration parameter

AI5

analog input 5, settable by way of the PTC, NTC, Pt 1000 probes configuration parameter

AI6

analog input 6, settable by way of the PTC, NTC, Pt 1000 probes configuration parameter

GND

analog inputs ground

+5V

0-5 V (5VDC) ratiometric transducers power supply

+24V

0-20 mA, 4-20 mA and 0-10 V (24 VAC) transducers power supply

DIGITAL INPUTS

Digital inputs.

PART

MEANING

DI1

digital input 1 (24 VAC/DC, 50/60 Hz or 2 KHz opto-isolated); the frequency can be set with the UNi-PRO 3 development

environment

DI2

digital input 2 (24 VAC/DC, 50/60 Hz o 2 KHz opto-isolated); the frequency can be set with the UNi-PRO 3 development

environment

DI3

digital input 3 (24 VAC/DC, 50/60 Hz opto-isolated)

DI4

digital input 4 (24 VAC/DC, 50/60 Hz opto-isolated)

DI5

digital input 5 (24 VAC/DC, 50/60 Hz opto-isolated)

COM

common digital inputs