beautypg.com

Gmx24-mft-x1 actuators, multi-function technology, Warning live electrical components, Master/slave – AERCO Belimo F7...HD/HDU Series Valve User Manual

Page 37

background image

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA

37

Wiring Diagrams

3

Actuators may also be powered by 24 VDC.

5

Actuators with plenum rated cable do not have numbers on wires; use
color coded instead. Actuators with appliance rated cable use numbers.

8

Control signal may be pulsed from either the Hot (Source) or
Common (Sink) 24 VAC line.

10

For triac sink the Common connection from the actuator must be
connected to the Hot connection of the controller.

Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.

9

Contact closures A & B also can be triacs. A & B should

both be closed for triac source and open for triac sink.

11

Position feedback cannot be used with a Triac sink controller. The
actuator internal common reference is not compatible.

WARNING Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, it may

be necessary to work with live electrical components. Have a qualifi ed licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.

GMX24-MFT-X1 Actuators, Multi-Function Technology

7

Blk

(1)

Common

Red

(2)

+ Hot

Wht

(3)

Y

1

Input, 2 to 10V

Org

(5)

U Output, 2 to 10V

4 to 20 mA

or

2 to 10 VDC

Control Signal

Line
Volts

24 VAC Transformer

(+)

(–)

Ω

500

Ω

1/4 watt

3

5

CCW CW

W

545_No_

2

VDC/4-20 mA

Blk

(1)

Common

Red

(2)

Hot

Wht

(3)

Y Input

Org

(5)

U Output

Line
Volts

24 VAC/DC Transformer

a

Position

Feedback VDC (+)

(–)

3

W545_No_

2

Two Position

CCW

CW

A

B

5

CCW

CW

A

B

5

Direction of rotation switch

Line
Volts

2 to 10 VDC

Feedback Signal

24 VAC Transformer

Blk

(1)

Common –

Red

(2)

Hot +

Wht

(3)

Y

1

Input

Org

(5)

U

Output 2 to 10V

Pnk

(4)

Y

2

Input

8

3

A

B

9

10

11

W545_No_2

Floating Point

Blk

(1)

Common

Red

(2)

+ Hot

Wht

(3)

Y Input

Org

(5)

U Output

Line
Volts

24 VAC Transformer (AC only)

(+)

(–)

8

Position

Feedback VDC

W

545_No_2

PWM

Blk (1) Common

Red (2) + Hot

Wht (3) Y

Input, 2 to 10 V

Org

(5) U

Output 2 to 10 V

CCW CW

Master

CCW CW

Slave

24 VAC Transformer

Line
Volts

Control Signal
2 to 10 VDC

(–)
(+)

3

5

Blk (1) Common

Red (2) + Hot

Wht (3) Y

Input, 2 to 10 V

Org

(5) U

5

Master

_S

la

ve

Master/Slave

0

7/10 - Subject to change. © Belimo Air

controls

(USA

), Inc

.

This manual is related to the following products: