GKB24-3-X1 Actuators, On/Off, Floating Point

Dimensions with 2-Way Valve

D

B

C

A

BHC

Dimensions (Inches)

Non-Fail

Safe (psi)

Valve

Size

A

B

C

D(Max) BHC

GK

F680HD

3”

1.78

7.00

7.00

16.53

6.00

200

F6100HDU

4”

2.05

8.00

8.00

17.53

7.50

50

F6125HDU

5”

2.14

8.00

8.00

18.03

8.50

50

F650-150SHP

2”

1.75

9.00

9.00

20.03

4.75

285

F665-150SHP

2½”

1.88

9.00

9.00

20.53

5.50

285

F680-150SHP

3”

1.92

9.00

9.00

21.03

6.00

285

F6100-150SHP

4”

2.13

9.00

9.00

21.53

7.50

150

F650-300SHP

2”

1.75

9.00

9.00

20.03

5.00

285

F665-300SHP

2½”

1.88

9.00

9.00

20.53

5.88

285

F680-300SHP

3”

1.92

9.00

9.00

21.03

6.63

285

F6100-300SHP

4”

2.13

9.00

9.00

21.53

7.88

150

AM_GM_LineRe

vise

d

Technical Data

GKB24-3-X1

Power supply

24VAC ±20% 50/60Hz
24VDC ±10%

Power consumption

12W (3W)

Transformer sizing

21VA (class 2 power source)

Electrical connection

18 GA plenum rated cable
½" conduit connector
protected NEMA 2 (IP54)
3 ft [1m] 10 ft [3m] 16 ft [5m]

Overload protection

electronic throughout 0 to 95 rotation

Operation range Y

on/off, fl oating point

Input impedance

100k

Ω (0.1 mA), 500Ω

1500

Ω (fl oating point, on/off)

Feedback output U

2 to 10VDC, 0.5mA max, VDC variable

Angle of rotation

max. 95°, adjustable with mechanical stop
electronically variable

Direction of rotation

reversible with

switch

Fail-safe position

adjustable with dial or tool 0 to 100% in 10%
increments

Position indication

refl ective visual indicator (snap-on)

Manual override

external push button

Running time

normal operation
fail-safe

150 seconds (default), variable 90 to 150 seconds
35 seconds

Humidity

5 to 95% RH non-condensing (EN 60730-1)

Ambient temperature

-22°F to +122°F [-30°C to +50°C]

Storage temperature

-40°F to +176°F [-40°C to +80°C]

Housing

NEMA2, IP54, UL enclosure type 2

Housing material

UL94-5VA

Agency list

cULus acc. to UL 60730-1A/-2-14
CAN/CSA E60730-1:02
CE acc. to 2004/108/EEC and 2006/95/EC

Noise level

< 45dB(A)

Servicing

maintenance free

Quality standard

ISO 9001

Dimensions (Inches)

Non-Fail

Safe (psi)

Valve

Size

A

B

C

D(Max) BHC

GM

F765HD

2½”

5.00

6.70

6.70

16.53

5.50

200

F780HDU

3”

5.50

7.20

7.20

16.78

6.00

50

F750-150SHP

2”

4.50

6.25

6.25

17.03

4.75

150

F765-150SHP

2½”

5.00

6.88

6.88

17.53

5.50

150

F780-150SHP

3”

5.50

7.42

7.42

18.03

6.00

150

F7100-150SHP

4”

6.50

8.63

8.63

18.53

7.50

150

Dimensions with 3-Way Valve

10

0

D

A

B

C

S

in

g

le_Butterfl

y

0

7/10 - Subject to change. © Belimo Air

controls (USA), Inc.

This manual is related to the following products: