W550

Observe class 1 and class 2 wiring restrictions.

Transformer sizing = SY actuator draw X 1.25 (safety margin)
(Ex. SY2-24 requires 3.0A x 1.25 = 3.75A,
3.75A X 24 VAC = 90VA Transformer).

Indicates an action or condition that may cause
irreversible damage to the actuator(s) or
associated equipment.

Equipment damage!
Power consumption and input impedance
must be observed.

CAUTION

Indicates a potentially hazardous situation which, if
not avoided, may result in minor or moderate injury.
It may also be used to alert against unsafe practices.

Warnings and Cautions appear at appropriate
sections throughout this manual. Read these carefully.

Hazard Identification

33

33

INSTALLATION NOTES

24 VAC Transformer

Line
Volts

G Ground

4 Power Supply Com

5 Power Supply Hot

6 Control Signal (-)

7 Control Signal (+)

8 Internal Use Only

9 Internal Use Only

10 Internal Use Only

11 Feedback (-)

12 Feedback (+)

Feedback (B)

G Ground

4 Power Supply Com

5 Power Supply Hot

6 Control Signal (-)

7 Control Signal (+)

8 Internal Use Only

9 Internal Use Only

10 Internal Use Only

11 Feedback (-)

12 Feedback (+)

SY1 -24P

24 VAC Transformer

Line
Volts

Feedback (A)

Control Signal

Actuator B

Actuator A

Use of feedback is optional.

APPLICATION NOTES

Recommended twisted shielded pair for control wiring.
Ground shielded wire at control panel chassis.
Tape back ground at actuator.

SY1 -24P

A

B

C

E

F

Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.

A-B (Open Indication)

LS4

LS3

A-E (Closed Indication)

A

B

C

E

F

Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.

A-B (Open Indication)

LS4

LS3

A-E (Closed Indication)

NOTES SY1-24P

Each actuator should be powered by a single, isolated
control transformer.

s

"–" wiring to a common is prohibited. Terminals 4 and 6 need to
be wired separately otherwise irreversible damage will occur.

s

G

G

35

36

33

35

36

35

36

Actuators: SY1-24P

Wiring for Control Valves
Proportional, 24V

0

7/10 - Subject to change. © Belimo Air