Mechanical data

751134

751184

Dimensions

Height

100,0 mm

100,0 mm

Width

22,5 mm

22,5 mm

Depth

120,0 mm

120,0 mm

Weight

215 g

190 g

The standards current on 2009­12 apply.

Safety characteristic data

Operating
mode

EN ISO
13849­1:
2008

PL

EN ISO
13849­1:
2008

Category

EN IEC
62061

SIL CL

EN IEC
62061

PFH

D

 [1/h]

IEC 61511

SIL

IEC 61511

PFD

EN ISO
13849­1:
2008

T

M

 [year]

Safety con­
tacts, in­
stantaneous PL e

Cat. 4

SIL CL 3

2,31E­09

SIL 3

2,03E­06

20

All the units used within a safety function must be considered when calculating the safety
characteristic data.

INFORMATION

A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.

CAUTION!

It is essential to consider the relay's service life graphs. The relay outputs'
safety­related characteristic data is only valid if the values in the service life
graphs are met.

The PFH value depends on the switching frequency and the load on the relay output. If the
service life graphs are not accessible, the stated PFH value can be used irrespective of the
switching frequency and the load, as the PFH value already considers the relay's B10d
value as well as the failure rates of the other components.