Pilz PNOZ s4 C 48-240VACDC 3 n/o 1 n/c User Manual
Page 21

PNOZ s4
Operating Manual PNOZ s4
21396EN13
21
Electrical data
751134
751184
Max. overall cable resistance Rl
max
Singlechannel at UB DC
30 Ohm
30 Ohm
Singlechannel at UB AC
30 Ohm
–
Dualchannel without detection
of shorts across contacts at UB
DC
30 Ohm
60 Ohm
Dualchannel without detection
of shorts across contacts at UB
AC
30 Ohm
–
Dualchannel with detection of
shorts across contacts at UB DC 30 Ohm
30 Ohm
Dualchannel with detection of
shorts across contacts at UB AC 30 Ohm
–
Min. input resistance at poweron
110 Ohm
110 Ohm
Voltage at
Input circuit DC
24,0 V
24,0 V
Start circuit DC
24,0 V
24,0 V
Feedback loop DC
24,0 V
24,0 V
Current at
Input circuit DC
50,0 mA
50,0 mA
Start circuit DC
50,0 mA
50,0 mA
Feedback loop
50,0 mA
50,0 mA
Number of output contacts
Safety contacts (N/O), instant
aneous
3
3
Auxiliary contacts (N/C)
1
1
Inputs
751134
751184
Number
2
2
Semiconductor outputs
751134
751184
Number
1
1
Voltage
24,0 V
24,0 V
Current
20 mA
20 mA
Relay outputs
751134
751184
Max. short circuit current IK
1 kA
1 kA