beautypg.com

Technical details – Pilz PNOZ s4 C 48-240VACDC 3 n/o 1 n/c User Manual

Page 14

background image

PNOZ s4

Operating Manual PNOZ s4
21396­EN­13

14

U

B

 48­240 VAC/DC

Example

}

Inductive load: 0,2 A

}

Utilisation category: AC15

}

Contact service life: 1,000,000 cycles

Provided the application requires fewer than 1,000,000 cycles, the PFH value (see tech­
nical details) can be used in the calculation.

To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With contact­
ors, use freewheel diodes for spark suppression.

Technical details

Order no. 750104 ─ 751104

See below for more order numbers

General

750104

750134

751104

Approvals

CCC, CE, EAC (Euras­
ian), KOSHA, TÜV,
cULus Listed

CCC, CE, EAC (Euras­
ian), KOSHA, TÜV,
cULus Listed

CCC, CE, EAC (Euras­
ian), KOSHA, TÜV,
cULus Listed