beautypg.com

Pilz PNOZ s4 C 48-240VACDC 3 n/o 1 n/c User Manual

Page 23

background image

PNOZ s4

Operating Manual PNOZ s4
21396­EN­13

23

Conventional thermal current
while loading several contacts

751134

751184

Ith per contact at UB AC

Conv. therm. current with 1 con­
tact

6,00 A

Conv. therm. current with 2 con­
tacts

6,00 A

Conv. therm. current with 3 con­
tacts

4,50 A

Ith per contact at UB DC

Conv. therm. current with 1 con­
tact

6,00 A

6,00 A

Conv. therm. current with 2 con­
tacts

6,00 A

6,00 A

Conv. therm. current with 3 con­
tacts

4,50 A

5,00 A

Times

751134

751184

Switch­on delay

With automatic start typ.

170 ms

170 ms

With automatic start max.

300 ms

300 ms

With automatic start after power
on typ.

350 ms

350 ms

With automatic start after power
on max.

600 ms

600 ms

With manual start typ.

40 ms

40 ms

With monitored start with rising
edge typ.

35 ms

35 ms

With monitored start with rising
edge max.

50 ms

50 ms

With monitored start with falling
edge typ.

55 ms

55 ms

With monitored start with falling
edge max.

70 ms

70 ms

Delay­on de­energisation

With E­STOP typ.

10 ms

10 ms

With E­STOP max.

20 ms

20 ms

With power failure typ.

40 ms

With power failure max.

80 ms

With power failure typ. UB 240 V 300 ms

With power failure max. UB 240
V

450 ms

Recovery time at max. switching
frequency 1/s

After E­STOP

50 ms

100 ms

After power failure

100 ms

100 ms

Waiting period with a monitored
start

With rising edge

120 ms

120 ms

With falling edge

150 ms

250 ms