Pilz PNOZ s4 C 48-240VACDC 3 n/o 1 n/c User Manual
Page 23

PNOZ s4
Operating Manual PNOZ s4
21396EN13
23
Conventional thermal current
while loading several contacts
751134
751184
Ith per contact at UB AC
Conv. therm. current with 1 con
tact
6,00 A
–
Conv. therm. current with 2 con
tacts
6,00 A
–
Conv. therm. current with 3 con
tacts
4,50 A
–
Ith per contact at UB DC
Conv. therm. current with 1 con
tact
6,00 A
6,00 A
Conv. therm. current with 2 con
tacts
6,00 A
6,00 A
Conv. therm. current with 3 con
tacts
4,50 A
5,00 A
Times
751134
751184
Switchon delay
With automatic start typ.
170 ms
170 ms
With automatic start max.
300 ms
300 ms
With automatic start after power
on typ.
350 ms
350 ms
With automatic start after power
on max.
600 ms
600 ms
With manual start typ.
40 ms
40 ms
With monitored start with rising
edge typ.
35 ms
35 ms
With monitored start with rising
edge max.
50 ms
50 ms
With monitored start with falling
edge typ.
55 ms
55 ms
With monitored start with falling
edge max.
70 ms
70 ms
Delayon deenergisation
With ESTOP typ.
10 ms
10 ms
With ESTOP max.
20 ms
20 ms
With power failure typ.
–
40 ms
With power failure max.
–
80 ms
With power failure typ. UB 240 V 300 ms
–
With power failure max. UB 240
V
450 ms
–
Recovery time at max. switching
frequency 1/s
After ESTOP
50 ms
100 ms
After power failure
100 ms
100 ms
Waiting period with a monitored
start
With rising edge
120 ms
120 ms
With falling edge
150 ms
250 ms