PNOZ s4

Operating Manual PNOZ s4
21396­EN­13

12

Fault 
Diagnostics: Internal error, unit defective

}

Remedy: Switch supply voltage off and then on again, change unit if neces­
sary.

Power 
Diagnostics: Supply voltage too low

}

Remedy: Check the supply voltage.

In1, In2 alternately

Fault
Diagnostics: Short detected between S12 and S22

}

Remedy: Rectify short across contacts, switch supply voltage off and then
on again.

In1

Fault
Diagnostics: Power­up blocked due to short­term interruption at S12; input cir­
cuits not operated simultaneously

}

Remedy: Open both input circuits, S12 and S22, simultaneously and then
close again.

In2

Fault
Diagnostics: Power­up blocked due to short­term interruption at S22; input cir­
cuits not operated simultaneously

}

Remedy: Open both input circuits, S12 and S22, simultaneously and then
close again.

Reset

Fault
Diagnostics: Position of rotary switch is not permitted or rotary switch was ad­
justed during operation.

}

Remedy: Switch supply voltage off and then on again.