Pilz PNOZ s4 C 48-240VACDC 3 n/o 1 n/c User Manual
Page 18

PNOZ s4
Operating Manual PNOZ s4
21396EN13
18
Times
750104
750134
751104
Switchon delay
With automatic start
typ.
170 ms
170 ms
170 ms
With automatic start
max.
300 ms
300 ms
300 ms
With automatic start
after power on typ.
350 ms
350 ms
350 ms
With automatic start
after power on max.
600 ms
600 ms
600 ms
With manual start typ.
40 ms
40 ms
40 ms
With monitored start
with rising edge typ.
35 ms
35 ms
35 ms
With monitored start
with rising edge max.
50 ms
50 ms
50 ms
With monitored start
with falling edge typ.
55 ms
55 ms
55 ms
With monitored start
with falling edge max.
70 ms
70 ms
70 ms
Delayon deenergisation
With ESTOP typ.
10 ms
10 ms
10 ms
With ESTOP max.
20 ms
20 ms
20 ms
With power failure typ. 40 ms
–
40 ms
With power failure max. 80 ms
–
80 ms
With power failure typ.
UB 240 V
–
300 ms
–
With power failure max.
UB 240 V
–
450 ms
–
Recovery time at max.
switching frequency 1/s
After ESTOP
100 ms
50 ms
100 ms
After power failure
100 ms
100 ms
100 ms
Waiting period with a
monitored start
With rising edge
120 ms
120 ms
120 ms
With falling edge
250 ms
150 ms
250 ms
Min. start pulse duration
with a monitored start
With rising edge
30 ms
30 ms
30 ms
With falling edge
100 ms
100 ms
100 ms
Supply interruption before
deenergisation
20 ms
20 ms
20 ms
Simultaneity, channel 1
and 2
∞
∞
∞
Environmental data
750104
750134
751104
Climatic suitability
EN 60068278
EN 60068278
EN 60068278
Ambient temperature
Temperature range
10 55 °C
10 55 °C
10 55 °C