5 reporting commands, 6 clear and reset commands, 7 parameter setting commands – Rice Lake Counterpart Configurable Counting Indicator - User Manual - Version 1.0 User Manual
Page 59: Reporting commands, Clear and reset commands, Parameter setting commands

Counterpart User Manual - Serial Commands
53
6.1.5
Reporting Commands
Reporting commands send specific information to the
serial port. The commands listed in Table 6-5 can be
used in all modes.
Transmitting all configuration settings can be
achieved by the DUMPALL command or by
pressing PRINT while in menu mode.
6.1.6
Clear and Reset Commands
The following commands can be used to clear and
reset the
Counterpart
:
RS
: Reset system. Resets the indicator without
resetting the configuration.
RESETCONFIGURATION
: Restores all
configuration parameters to their default values
(menu mode only). The
RESETCONFIGURATION
function can also be initiated by pre ssing
navigating to the
DEFALT
parameter under the
VERS menu and selecting YES. Then press
ENTER
to reset the indicator.
All load cell calibration settings are lost
w h e n t h e R E S E T C O N F I G U R AT I O N
command is run.
CLEARBUFFER
: Clears the buffer information.
6.1.7
Parameter Setting Commands
Parameter setting commands allow you to display or
change the current value for a particular configuration
parameter (Tables 6-6 through 6-12).
Current configuration parameter settings can be
displayed in all modes using the following syntax:
command
Most parameter values can be changed in menu mode
only.
Use the following command syntax when changing
parameter values:
command=value
, where
value
is either a number or a parameter value. Use no spaces
before or after the equal (=) sign. If you type an
incorrect command, the display reads
??
.
For example, to set the motion band parameter to 5
divisions, type the following:
SC.MOTBAND=5
For parameters with selectable values, enter the
command and equal sign followed by a question
mark:
command=?
to see a list of those values.
The indicator must be in menu mode to use this
function.
Some parameters are valid only if other
parameters or parameter values are
specified. Restrictions for front-panel
configuration also apply to serial command configuration.
Command
Function
DUMPALL
List all parameter values and ID
information
DUMPCONFIG
List all parameter values excluding ID
information
DUMPAUDIT
List audit trail information
DUMPIDS
List all ID information
DUMPIDINDEX
List a specific ID by index. See table 6-13
for more information.
DUMPIDCODE
List a specific ID by code. See table 6-13
for more information.
VERSION
Write
Counterpart
software version
P
Write current displayed weight with units
identifier. See Section 9.2.1 on page 67.
XE
Returns a 10-digit code representing any
error conditions currently shown on the
front panel.
Table 6-5. Reporting Commands
Note
Note
Note