beautypg.com

Alarm codes – Carrier 040-420 User Manual

Page 49

background image

Alarm Codes

Following is a detailed description of

each alarm code error and possible cause. Manual reset of

an alarm is accomplished by moving
STOP-CCN Switch to STOP position, then back to LO-
CAL or CCN position. See Table 14 for listing of each alarm
code.
Code 0

No alarms exist

Codes 1 8 Compressor failure

If DSIO-LV or -EXV relay module control relay feed-

back switch or signal is sensed as open during operation of

a compressor, microprocessor detects this and stops com-

pressor, energizes alarm light, and displays a code of

3, 4, 5, 6, 7, or 8 depending on the compressor. Compres-
sor locks off; to reset, use manual reset method.

If lead compressor in a circuit shuts down, the other com-

pressors in the circuit stop and lock off. Only the alarm
mode for lead compressor is displayed.

The microprocessor is also programmed to indicate com-

pressor failure if feedback terminal on DSIO-LV or -EXV

terminal strip receives voltage when compressor is not

supposed to be on.

Table 14

Alarm Codes

PROBABLE CAUSE

D E S C R I P T I O N

No Alarms Exist

ACTION TAKEN

B Y C O N T R O L

C K T

N o

Compressor Al failure

Circuit A shut down

Manual

Compressor A2, A3, A4 failure

Compressor shut down

Compressor failure

Circuit B shut down

Compressor

failure

Compressor shut down

Leaving water thermistor failure

Unit shut down

Entering water thermistor failure

Unit shut down

Compressor Al sensor failure

Circuit A shut down

Compressor

sensor failure

Circuit B shut down

Reset thermistor failure

Normal set point used

Manual

Manual

Manual

A u t o

A u t o

A u t o

A u t o

A u t o

Discharge pressure transducer failure, circuit A

Circuit A shut down

Discharge pressure transducer failure, circuit B

Circuit B shut down

Suction pressure transducer failure, circuit A

Circuit A shut down

Circuit B shut down

Circuit A shut down

Auto.

A u t o

Suction pressure transducer failure, circuit B

Oil pressure transducer failure, circuit A

Oil pressure transducer failure, circuit

Circuit B shut down

Transducer supply voltage low

Unit shut down

Interlock switch oaen

Unit shut down

Yes

N o

Yes

Yes

Yes

Yes

N o

Yes

N o

N o

N o

N O

N o

N o

N o

N o

N o

A u t o

Auto.

Auto.

A u t o

A u t o

Unit voltage low or PSI faulty

M a n u a l

Chilled water pump inoperative

4-20

reset input failure

Normal set point used

demand limit failure

Demand limit ignored

Loss of communication with DSIO-LV

Unit shut down

A u t o

A u t o

Auto.

Loss of communication with DSIO-EXV

Unit shut down

Loss of communication with 4

Out module

Unit shut down

N o

Yes

N o

N o

A u t o

A u t o

Not used

I

Low refrigerant pressure circuit A

Low refrigerant pressure circuit B

Low refrigerant charge, plugged filter

drier, faulty EXV

*

Low refri erant charge, plugged filter

drier. fau tv EXV

oil pressure

circuit A

Circuit A shut down

N o

N o

N o

Manual

Faulty EXV, transducer, or thermistor

M a n u a l

Faultv EXV, transducer, or thermistor.

Manual

oil pressure

c i r c u i t B

Circuit B shut down

N o

Manual

4 2

Cooler freeze protection

Unit shut down

4 3

Low cooler water flow

Unit shut down

Low suction temperature circuit A

Low suction temperature circuit B

Circuit A shut down
after 10 minutes

Circuit B shut down
afler

minutes

N o

N o

N o

N o

Manual

Manual

M a n u a l

High suction superheat circuit A

Circuit A shut down

Manual

Low charge, faulty EXV or

thermistor, or plugged filter drier

High suction superheat circuit B

Circuit B shut down

Yes

Yes

Low suction superheat circuit A

Low suction superheat circuit B

Illegal configuration

Circuit A shut down

Circuit shut down

Unit cannot start

Initial configuration required

Unit cannot start

Emergency stop by CCN command

Unit shut down

Yes

Yes

Yes

Manual

M a n u a l

Manual

Manual

Configuration error

M a n u a l

Configuration omitted

C C N

Network command.

DISPLAY

0

1

2 , 3 , 4

5

7,

9

1 0

1 9

2 0

2 1

2 2

2 3

2 4

2 5

2 6

2 7

2 8

2 9

3 0

3 2

3 3

3 4

3 5

3 6

3 7

3 8

3 9

4 0

4 1

4 4

4 5

4 6

4 7

4 8

4 9

5 1

5 2

High-pressure switch trip, discharge gas

thermostat trip, or wiring error

CPCS Ground Fault Protection

Thermistor or transducer failure

or wiring error.

Transducer failure or wiring error

Wiring error
or improper

or faulty module

address code

Low oil level, circuit breaker trip,

faulty EXV, crankcase heater,

or Pressure Transducer

Low oil level, circuit breaker trip,

fautty EXV, crankcase heater,
or

transducer

Low water flow or faulty thermistor

Chilled water pump failure
or faulty thermistor

Faulty EXV or thermistor

Faulty EXV or thermistor

Low charge, faulty EXV or
thermistor, or plugged filter drier.

Faulty EXV or thermistor

Faultv EXV or thermistor

L E G E N D

Compressor Protection Control Module

*Reset automatic first time, manual if repeated same day

Power Supply

49