Table 9 keypad directory, Status, Test – Carrier 040-420 User Manual
Page 32

Table 9
Keypad Directory
SUBFUNCTION
10 OUTPUTS
STATUS
DISPLAY
OUTPUTS
ALMR X
X
FRA2 X
X
FRB2 X
CHWP X*
X
ULA2 X*
X
ULB2 X*
E X V A X
E X V B X
X*
HGBB X
M M A X *
M M B X
TEST
COMMENT
Status of Outputs
Alarm Relay K3
Fan Relay
Fan Relay K2
Fan Relay K4
Fan Relay K5
Cooler Water Pump Relay K6
Unloader Al
Unloader
Unloader
Unloader
EXVA Percent Open
EXVB Percent Open
Hot Gas Bypass Relay Circuit A
Hot Gas Bypass Relay Circuit B
A Output Percent
Motormaster B Output Percent
To use Test function, LOCAL/ENABLE-STOP-CCN switch must be in STOP position To operate a test, scroll to desired test
Then, press
to start test. Press
to stop test.
SUBFUNCTION
KEYPAD ENTRY
OUTPUTS
DISPLAY
OUTPUTS
8 8 8.8.8 8.8.8
ALMR X
X
FRA2 X
X
X
CHWP X*
EXVA X
E X V B X
HGBRA X*
HGBRB X*
M M A X *
M M B X *
COMMENT
Test Outputs
Display Check
Energize Alarm Relay K3
Energize Fan Relay Al
Energize Fan Relay A2 K2
Energize Fan Relay
K4
Energize Fan Relay
K5
Energize Cooler Water Pump K6
Enter Desired EXVA Position
Enter Desired
Position
Energize Hot Gas Bypass Relay A
Energize Hot Gas
Relay B
Enter Desired
A Output Signal
Enter Desired Motormaster B Output Signal
32