Table 9 keypad directory test, Schedule, Can be – Carrier 040-420 User Manual

Page 33

background image

Table 9

Keypad Directory

TEST

SUBFUNCTION

KEYPAD ENTRY

2 COMPRESSORS AND

UNLOADERS

During compressor test, compressors start and run for

10 seconds. Compressor service valves and liquid line

valves must be open. Energize crankcase heaters 24 hours
prior to performing compressor tests.

DISPLAY

C O M P

CPA1 X

CPA2 X*

CPA3 X*

CPA4 X*

X

x*

CPB3 X*

CPB4 X*

X

ULA2 X*

X

ULB2 X*

SCHEDULE

COMMENT

Compressor and Unloader Test

Test Compressor Al

Test Compressor

Test Compressor

Test Compressor

Test Compressor

Test Compressor

Test Compressor

Test Compressor

Energize Unloader Al

Energize Unloader

Energize Unloader

Energize Unloader

T h e S c h e d u l e f u n c t i o n k e y

is used to configure the occupancy schedule The clock select subfunction

can be

used for

unoccupied shutdown or unoccupied setback depending on the cooling set point control configuration. The Schedule function
described is for clock which is the internal clock. Password required for all subfunctions except override.

SUBFUNCTION

1

KEYPAD ENTRY

I

DISPLAY

I

COMMENT

1 OVERRIDE

OVRD X

Number of Override Hrs (0 4 Hrs)

For example, to extend current occupied mode for 3 hrs, press:

OVRD 3

Extended Occupied Time

2 CLOCK SELECT

CLOCK XX

Type of Clock Control

0 = No Clock, 1 = Clock 1 (Internal)

LEGEND

*Must be configured

Carrier Comfort Network

a p p l i c a b l e .

Electronic Expansion Valve

M O P

Maximum Operating Pressure

33