Table 10

Operationat and Mode Display Codes

The operating modes are displayed by name or code num-

ber, to indicate the operating status of the unit at a given
time. The modes are:

STATUS FUNCTION This function shows the rotating
display, current status of alarm (diagnostic) codes, capacity
stages, operating modes, chilled water set point, all meas-
ured system temperatures and pressures, superheat values,
pressure switch positions, analog inputs, and switch inputs.
These subfunctions are defined on pages 37 and 38.

( R o t a t i n g D i s p l a y )

(Alarms)

Alarms are messages that one or more

faults have been detected. Each fault is assigned a code num-
ber which is reported with the alarm. See Table 10 for code
definitions. The codes indicate failures that cause the unit
to shut down, terminate an option (such as reset) or result
in the use of a default value

as

set point.

Up to 5 alarm codes can be stored at once. To view them

in sequence, press

to enter the alarm displays

and then press

q

to move to the individual alarm dis-

plays. Press

q

after a code has been displayed. The mean-

ing of the code scrolls across the screen. See Example

Example 1

Reading Alarm Codes

CODE

Unit is off. LOCAL/ENABLE-STOP-CCN switch is
in OFF position, or LOCAL/ENABLE-STOP-CCN

switch may be in LOCAL position with external ON/

OFF switch in OFF position

LOCAL OFF

CLOCK OFF

CCN OFF

Unit is off due to CCN network command. LOCAL/
ENABLE-STOP-CCN switch is in CCN position.

Unit is off due to internal clock schedule. LOCAL/
ENABLE-STOP-CCN switch is in LOCAL position.

Unit is on. LOCAL/ENABLE-STOP-CCN switch is
in LOCAL position If external ON/OFF switch is used,
i t w i l l b e i n O N b o s i t i o n .

LOCAL ON

CCN ON

Unit is on due CCN command
STOP-CCN switch is in CCN position.

Unit is on due to internal clock schedule or

CLOCK ON

pied override function.
CCN switch is in LOCAL position.

Dual set point is in effect In this mode, unit contin-
ues to run in unoccupied condition, but leaving wa-

ter set point is automatically increased to a higher

level

set

is in SET function)

Temperature reset is in effect. In this mode, unit is

using temperature reset to adjust leaving water set
point upward, and unit is currently controlling to the
modified set point. The set point can be modified
based on return water, outdoor-air temperature or
space temperature

M O D E 7

Demand limit is in effect. This indicates that ca-
p a c i t y o f u n i t i s b e i n g l i m i t e d b y d e m a n d l i m i t c o n -

trol option Because of this limitation, unit may

not be able to produce the desired leaving water

temperature

L o a d l i m i t i s i n e f f e c t . T h i s i n d i c a t e s t h a t c a p a c i t y o f
a system of units is being limited by a CCN

shed command Due to this limitation, unit may

not be able to produce the desired leaving water

temperature.

Not

K

E Y P A D

ENTRY

COMMENTS

MODE 8

DISPLAY

RESPONSE

0 S T A G E S
2 ALARMS

2 A L A R M S

A L A R M 9

COOLER LEAVING

FLUID THERMISTOR
F A I L U R E

A L A R M 4 2

COOLER FREEZE

P R O T E C T I O N

Keypad has not been used for

a t l e a s t 1 0 m i n u t e s . A l t e r n a t i n g
summary display appears on
screen

2 alarms detected

First alarm code

Explanation of alarm code

Second alarm code Cooler

freeze protection

Explanation of alarm code

MODE 9

MODE 10

MODE II

Ramp load (pulldown) limiting is in effect. In this mode,

the

at

leaving water temperature is dropped

is limited to a predetermined value to prevent com-
pressor overloading, See CRAMP set point in the
S E T f u n c t i o n i n T a b l e 9 T h e

l i m i t c a n b e

modified, if desired, to any rate from 2 F to 2 F

to

MODE 12

When a diagnostic (alarm) code is stored in the display

and the machine automatically resets, the code is deleted.
Codes for safeties which do not automatically reset are not
deleted until the problem is corrected and the machine is
switched to STOP, then back to LOCAL/ENABLE or CCN.

Timed override is in effect This is a 1 to 4 hour
temporary override of the programmed schedule,
forcing unit to occupied mode Override can be im-

plemented with unit under LOCAL or CCN control
Override expires after each use

MODE 13

MODE 14

Low cooler suction protection is in effect In this mode,
circuit capacity is not allowed to increase if cooler

saturated suction temperature is

F

C) for

water or 30” F (16” C) for brine or more below

leav-

ing fluid temperature, and saturated suction tem-
perature is less than 32 F

C). If these conditions

p e r s i s t b e y o n d 1 0 m i n u t e s , c i r c u i t i s s h u t d o w n a n d

fault code 44 or 45 is displayed.

CCN

CarrierComfort Network

(Modes)

The operating mode codes are dis-

played to indicate the operating status of the unit at a given
time. See Table 10.

To enter the MODES subfunction, depress

and

use

the

q

key to determine if more than one mode ap-

plies. See Example 2

to

read current mode with expansion.

37