P. Lateral Duct System (optional):

The lateral duct system shall allow one system to

heat or cool two adjacent rooms, with up to a

maximum of 30% of the discharge air being

diverted to the adjoining room (a return air path

must be provided from the adjoining room). The

lateral duct kit consists of two main components,

the plenum and the extension duct. In addition, the

kit includes an adjustable chassis discharge air

grille, adjustable wall register and decorative wall

molding for duct extension.
The lateral duct system shall be adaptable for either

right or left side ducting, with a maximum duct

extension of 4 feet. The duct run must be straight

and horizontal; no bends or turns.

Q. Accessories:

1. Insulated Polymer Wall Sleeve (P/N:

SLEEVE-INSUL-1PK) shall be made from a

molded polymer, with factory-installed Styro-

foam insulation and a minimum flammability

rating of UL94-5V. The sleeve surface shall be

textured to prevent shine and hide scratches.

2. Deep Wall Metal Wall Sleeve (up to 28-in.)

(P/N: SLEEVE-EXTxx-1PK) shall be a one-

piece, extended wall sleeve, with factory

installed insulation and deep wall baffles

integrated.

3. Sleeve Molding (P/N: SLEEVE-MOLDING)

shall trim the wall sleeve to the existing wall to

hide wall joints and irregularities due to the

sleeve opening.

4. Architectural Grille (P/N: GRILLE-PLA-

xxxxx or GRILLE-ALU-xxxxx) shall be poly-

meric for long durable life or painted alumi-

num for a superior color match to the building.

5. Subbase (P/N: SUBBASE-xxxV-xxA) shall be

pre-assembled from the factory and UL listed.

Subbase options include:
Non-electrical subbase: The non-electrical

subbase shall be pre-assembled and provides

mechanical support and requires no wiring.
Electrical subbase: The electrical subbase

shall be pre-assembled with factory-installed

electrical junction box containing a receptacle

for corded units.
Hardwired subbase: The hardwired electrical

subbase shall be pre-assembled with factory

installed electrical junction box containing

19 in. of flexible conduit (for a perfect fit to the

unit) and all mating connections.

6. Leveling Legs (P/N: LEVELING-LEGS) shall

attach easily to Carrier’s wall sleeve to provide

accurate, adjustable leveling and support to

units without a subbase.

7. Hardwire Kit (P/N: HARDWIRE-KIT) shall

provide a permanent connection to the unit.

The hardwire kit mounts on the front right side

of the unit and shall have 36 in. of flexible steel

conduit and a Molex connector for easy

connect/disconnect.

8. Conduit Interface Kit (P/N: CONDUIT-INTF-

4PK) shall provide wire connection to the unit

to interface with field-supplied conduit.

9. Condensate Drain (P/N: DRAIN-KIT-4PK) kit

shall be used internally or externally to route

excess condensate to a drainage system. It can

be field-installed on any Carrier wall sleeve.

The drain kit shall be attached to the exterior

right or left side of the wall sleeve for external

draining or may be mounted to the bottom of

the wall sleeve for internal draining.

10. Lateral Duct (P/N: LATERAL-DUCT) kit

shall include an adapter plenum, extension

duct, wall register and wall molding. The lat-

eral duct system allows one system to heat or

cool two adjacent rooms, by directing up to

30% of the airflow to the adjacent room.

11. Energy Management (P/N: EM-KIT) shall

allow individual units to be turned on and off

from a remote location or by a motion sensing

device. This kit interfaces to most energy man-

agement systems.

12. Lateral Air Deflector (P/N: DEFLECTOR-

1PK) shall allow right or left air distribution

from the chassis. Lateral air deflectors are rec-

ommended for units mounted in a corner or

off-center in a room.

13. Curtain Deflector (P/N: CURTDEL-52CP-

1PK) shall prevent curtains from being blown

into the discharge air.

14. Security door (P/N: SECURITY-DOOR) kit

shall prevent unauthorized access to the unit’s

heating and cooling controls and prevents

tampering with units in public locations and

institutions. The security door shall include

two matching keys and keys shall be common

to all Carrier Security Door kits.

15. Wall Thermostats (P/N: TSTATCCBxx01-B)

shall operate with 24 VAC, be digital and

non-programmable, easy-to-use and provide

maximum guest comfort.

16. Sleeve Molding (P/N: SLEEVE-MOLDING)

shall trim the wall sleeve to the existing wall to

hide wall joints and irregularities due to the

sleeve opening.

17. Power Fresh Air Vent (P/N: PWR-VENT-

DOORxxx) kit shall provide approximately

95 cfm of outdoor air for ventilation into the

room. The kit shall have an automatically door

that opens when the fan is on and closes when

the fan is off.