axial flow design, with integrated slinger ring. The

indoor fan shall be a dynamically balanced, poly-

mer, reverse curve blower wheel, to assure uniform

air distribution. The fan motor shall be of an

enclosed design to reduce the effects of moisture

and corrosion.

D. Compressor and Refrigerant:

The rotary-type compressor shall be fully hermetic

with internal and external vibration isolation. The

refrigeration system will be sealed and contain a

full refrigerant charge (R-22).

E. Coils:

Condenser and evaporator coils to be constructed of

high-efficiency, 11-element lance sine wave

enhanced aluminum fins and

3

/

8

-in. seamless axial

grooved copper tubing, necessary to achieve

EER and COP rating, as specified on the chassis

nameplate.

F. Factory-Installed Electric Heater:

The factory-installed, open coil type, electric heater

is standard in heat/cool and heat pump chassis. The

electric heater shall contain both an automatic reset

and a one-shot overtemperature protection device.

The heating capacity of the electric heater shall be

as identified on the contract drawing schedule and

in the specifications.

G. Controls:

All standard models shall be equipped with electro-

mechanical controls to simplify the serviceability of

the unit.

1. The chassis shall have standard controls,

accessible and covered by a hinged door. The

mode selection control shall consist of a

mechanical rotary selector switch, which pro-

vides OFF, FAN ONLY, HEAT or COOL oper-

ations. The temperature selection control shall

be an adjustable thermostat with upper and

lower limits.

2. All standard models shall have a continuous/

fan cycle selector switch located behind the

front panel. It shall allow the selection of con-

tinuous fan operation for maximum comfort or

cycle operation (fan only runs with cooling

or heating operation) for maximum energy

savings.

3. All standard models shall have a temperature

limiter control located behind the front panel.

The temperature limiter allows a room temper-

ature range to be set, to avoid extreme temper-

ature settings, to maximize energy savings.

4. Emergency Heat switch (heat pump models

only) shall disable the compressor in heating

mode and only allow the use of electric

heat during heating cycles. The Emergency

Heat switch is active at all outdoor ambient

temperatures.

5. Wall thermostat chassis (RC and RP models)

shall come from the factory ready for wall

thermostat installation, including a blank out

plate in place of the control knobs. No field-

installed kits or wire harnesses shall be

required.

6. Wall thermostat chassis (RC and RP models)

shall have a user selectable fan speed control

switch, on the control panel, to optimize fan

speed for maximum comfort.

H. Safeties:

Compressor shall have automatic reset, overtem-

perature and overcurrent protection. The fan motor

shall have an inherent, automatic reset overtemper-

ature protection. The electric heater shall have two

overtemperature protectors.

I.

Front Panel (supplied with chassis):
Front panel shall be constructed of a polymer mate-

rial to resist breakage and corrosion. It shall have a

front louvered surface with integrated control

door and air filters. The air filters shall be easily

accessible without removing the front panel from

the chassis.

J. Anti-Theft Control Knobs:

All chassis knobs shall resist breakage and corro-

sion. They shall be mounted on to the control box

section and captured behind the front panel, to pre-

vent unauthorized removal.

K. Bi-Directional Discharge Grille:

Bi-directional polymer discharge grille shall resist

corrosion and breakage. It shall be easily set to

direct air at 40 degrees from horizontal or

80 degrees from horizontal. This non-metallic dis-

charge grille shall be cool to the touch during the

heating cycle.

L. Ventilation:

The chassis shall have a manual adjustable fresh air

vent with a concealed manual control. The vent

control shall allow a maximum of 50 cfm of fresh

air to be drawn into the room when the indoor fan is

operating and the door is open. The ventilation air

can be increased to approximately 95 cfm by add-

ing the Power Fresh Air Vent accessory kit (see

section Q.17).

M. High-Efficiency Condensate Removal System:

The chassis shall have a condensate removal sys-

tem consisting of a condensate suction port, to draw

and atomize condensate, and a slinger ring inte-

grated in the outdoor fan, to disperse condensate

onto the condenser coil to be evaporated.

N. Snow Baffle:

The chassis shall contain a snow baffle to prevent

melting snow from freezing and potentially damag-

ing the outdoor fan.

O. Corrosion Protection (CP and RP Models Only):

Chassis with Corrosion Protection (CP,RP) shall be

used for coastal or corrosive environments, to pro-

long the life of the product. Minimum requirements

are:

1. All outdoor-exposed sheet metal parts shall be

coated with a polyester powder coat paint.

2. Compressor and outdoor-fan motor finish shall

be capable of withstanding 500 hours of salt

spray testing per ASTM B-117.

3. Compressor mounting screws shall be

SermaGuard™ coated.

4. Outdoor coil fin stock shall be coated and able

to withstand 1000 hours of salt spray testing

per ASTM B-117.

5. Outdoor coil tube sheets shall be made of 316L

stainless steel.