VIEW MENU

Mode

Item Field

Range

Access

Description

1

OFF, -4°F (-20.0°C)

to Setpoint Maximum

(variable)

USEr

InST

ADV

SET SETPOINT (ON / OFF)

SECTION A

Display the desired temperature.

2

OFF, -4°F (-20.0°C)

to Hot Tub Maximum

(variable)

USEr

InST

ADV

SET HOT TUB

SECTION B

Display the desired temperature.

3

OFF, -4°F (-20.0°C)

to DHW Maximum

(variable)

USEr

InST

ADV

SET DHW

SECTION C

Display the desired temperature.

4

OFF, -4°F (-20.0°C)

to Setpoint Maximum

(variable)

USEr

InST

ADV

SET SETPOINT (PWM)

SECTION D

Display the desired temperature.

5

OFF, -4°F (-20.0°C)

to Floor Maximum

(variable)

USEr

InST

ADV

SET FLOOR

SECTION E

Display the desired temperature.

6

OFF, -4°F (-20.0°C)

to Pool Maximum

(variable)

USEr

InST

ADV

SET POOL

SECTION F

Display the desired temperature.

1
2
3
4
5
6

-31 to 266°F

(-35.0 to 130.0°C)

SEC

LTD

USEr

InST

ADV

OUTDOOR

SECTION R

Displays the measured outdoor temperature.

Note:

This item is only available when the setpoint

control is connected to a tN4 bus and the Outdoor
item in the ADJUST menu is set to On.

1
2
3
4
5
6

-31 to 266°F

(-35.0 to 130.0°C)

InST

ADV

SUPPLY TEMP OF tN4 BUS

SECTION R

Actual water temperature of the tN4 bus for
heating.
Note: This item is only available when the

setpoint control is connected to a tN4 System
Control, DIP switch 2 is set to tN4 System
Control, and the Heat Source item in the ADJUST
menu is set to hydronic (HYDr).

VIEW Menu (2 of 2)

After the last item, the control returns to the first item in the menu.