Adjus t menu – tekmar 162 Setpoint Control Installation User Manual

Page 10

background image

© 2007

D 162 - 08/07

10 of 32

ADJUST Menu (2 of 6)

Mode

Item Field

Range

Access

Description

2

OFF, 40°F

(4.5°C) to Hot Tub

Maximum

Default = 95°F

(35.0°C)

USEr

InST

ADV

SET HOT TUB UNOCCUPIED

SECTION

B

Select the hot tub temperature for the unoccupied
period.

Note:

This item is only available when a

programmable setback schedule has been
selected.

2

OFF, 40°F

(4.5°C) to Hot Tub

Maximum

Default = 50°F

(10.0°C)

USEr

InST

ADV

SET HOT TUB AWAY

SECTION

B

Select the hot tub temperature for the away
period.

Note:

This item is only available when scenes

are set to On.

3

OFF, 40°F (4.5°C)
to DHW Maximum

Default = 130°F

(54.5°C)

LTD

USEr

InST

ADV

SET DHW TANK OCCUPIED

SECTION

C

Select the indirect domestic hot water tank
temperature for the occupied period.
Note:

In the Limited Access Level, the temperature

can only be adjusted by +/-3°F (1.5°C) from the
temperature setting entered prior to entering the
Limited access level.

3

OFF, 40°F (4.5°C)
to DHW Maximum

Default = 110°F

(43.5°C)

USEr

InST

ADV

SET DHW TANK UNOCCUPIED

SECTION

C

Select the indirect domestic hot water tank
temperature for the unoccupied period.

Note:

This item is only available when a

programmable setback schedule has been
selected.

3

OFF, 40°F (4.5°C)
to DHW Maximum

Default = OFF

USEr

InST

ADV

SET DHW TANK AWAY

SECTION

C

Select the indirect domestic hot water tank
temperature for the away period.

Note:

This item is only available when scenes

are to set to On.

5

OFF, 40°F (4.5°C)

to Floor Maximum

Default = 80°F

(26.5°C)

LTD

USEr

InST

ADV

SET FLOOR OCCUPIED

SECTION

E

Select the floor temperature for the occupied
period.
Note:

In the Limited Access Level, the temperature

can only be adjusted by +/-3°F (1.5°C) from the
temperature setting entered prior to entering the
Limited access level.

5

OFF, 40°F (4.5°C)

to Floor Maximum

Default = 70°F

(21.0°C)

USEr

InST

ADV

SET FLOOR UNOCCUPIED

SECTION

E

Select the floor temperature for the unoccupied
period.
Note:

This item is only available when a

programmable setback schedule has been
selected.

5

OFF, 40°F (4.5°C)

to Floor Maximum

Default = OFF

USEr

InST

ADV

SET FLOOR AWAY

SECTION

E

Select the floor temperature for the away
period.

Note:

This item is only available when scenes

are set to On.

ADJUS

T MENU

Continued on next page.