tekmar 162 Setpoint Control Installation User Manual
Page 30

© 2007
D 162 - 08/07
30 of 32
Error Messages (1 of 2)
Error Message
Description
ADJUST ERROR
The setpoint control failed to read the ADJUST menu settings from memory and has reloaded
the factory default settings. Operation stops until the ADJUST menu settings are checked.
Note: To clear the error, the access level must be set to Advanced before checking the
settings in the ADJUST menu.
TIME ERROR
The setpoint control failed to read the TIME menu settings from memory and has reloaded
the factory default settings. The setpoint control continues to operate while displaying this
error.
Note: To clear the error, the access level must be set to Advanced before checking the
settings in the TIME menu.
SCENE ERROR
The setpoint control failed to read the SCENE menu settings from memory and has reloaded
the factory default settings. The setpoint control continues to operate while displaying this
error.
Note: To clear the error, the access level must be set to Advanced before checking the
settings in the SCENE menu.
SCHEDULE ERROR
The setpoint control failed to read the SCHEDULE menu settings from memory and has
reloaded the factory default settings. The setpoint control continues to operate while displaying
this error.
Note: To clear the error, the access level must be set to Advanced before checking the
settings in the SCHEDULE menu.
MISCELLANEOUS ERROR
The setpoint control failed to read the MISCELLANEOUS menu settings from memory and
has reloaded the factory default settings. The setpoint control continues to operate while
displaying this error.
Note: To clear the error, the access level must be set to Advanced before checking the
settings in the MISCELLANEOUS menu.
BUS ERROR
Due to an open or short circuit, communication is lost with the tN4 bus. Check the wires for
damage or loose connections. Check the wires for continuity. The error message will clear
once the error condition has been corrected.
Note: In some cases, the setpoint control is intentionally removed from the tN4 system. Press
the Up and Down buttons together to clear the address and set Dip 2 to the ‘None’ position.
This will also clear the bus error message.
NO tN4 SYSTEM CONTROL
DIP switch 2 is set to tN4 System Control and the setpoint control does not detect the tN4 System
Control. Once the tN4 System Control is detected, this error will clear automatically.
Note: If a tN4 System Control is not installed, set the tN4 System Control DIP switch 2 to
None.
ADDRESS ERROR
Two tN4 devices have been manually set to the same address. The setpoint control continues
to operate with this error but does not communicate with the tN4 bus. To clear this error,
manually select an unused address. This can be done automatically by setting the Address
item to Auto.
Note: Error Messages are only visible while in the Advanced or Installer access level.