ADJUST Menu (4 of 6)

Mode

Item Field

Range

Access

Description

1
2
3

0 to 20:00 min in

10 sec increments

Default = 0:30

ADV

MINIMUM ON

SECTION

H

Select the minimum on time of relays R1 and R2.
This helps prevent short cycling.

1
2
3

0 to 20:00 min in

10 sec increments

Default = 0:30

ADV

MINIMUM OFF

SECTION

H

Select the minimum off time of relays R1 and R2.
This helps prevent short cycling.

1
2
3
4
5
6

HYDr, OTHr

Default = HYDr

InST

ADV

HEAT SOURCE

SECTION

R

Select whether the heat source is hydronic
(HYDr) or other (OTHr) when the setpoint control
is connected to a tN4 System Control.
Note:

This item is only available when DIP switch

2 is set to tN4 System Control and the mode of
operation is set to Heat.

1
2
3
4
5
6

60 to 220°F

(15.5 to 104.5°C)

Default = 180°F

(82.0°C)

InST

ADV

EXCHANGE SUPPLY OCCUPIED

SECTION R

Select the desired supply water temperature
required on the tN4 bus to heat the setpoint load
during the occupied period.
Note:

This item is only available when DIP

switch 2 is set to tN4 System Control, the mode
of operation is set to Heat, and the Heat Source
item in the ADJUST menu is set to hydronic
(HYDr).

1
2
3
4
5
6

80 to 220°F

(26.5 to 104.5°C)

Default = 200°F

(93.5°C)

ADV

MAXIMUM SUPPLY

SECTION

R

Select the maximum exchange supply water
temperature allowed on the tN4 bus to heat the
setpoint load.
Note:

This item is only available when DIP switch

2 is set to tN4 System Control, the mode of
operation is set to Heat, and the Heat Source
item in the ADJUST menu is set to hydronic
(HYDr).

1
2
3
4
5
6

STAT, OFF, LO,

MED, HI

Default = OFF

InST

ADV

PRIORITY

SECTION

R

Select the priority level of the setpoint control
over other devices on the tN4 system.
Note:

This item is only available when DIP switch

2 is set to tN4 System Control, the mode of
operation is set to Heat, and the Heat Source
item in the ADJUST menu is set to hydronic
(HYDr).

Note:

STAT, OFF, LO, MED, HI are available when

the control is connected to a boiler bus.

STAT and OFF are available when the control is
connected to a mix bus.

ADJUS

T MENU

Continued on next page.