Adjus t menu – tekmar 162 Setpoint Control Installation User Manual
Page 13

13 of 32
© 2007
D 162 - 08/07
ADJUST Menu (5 of 6)
Mode
Item Field
Range
Access
Description
1
2
3
4
5
6
OFF, On
Default = On
InST
ADV
RELAY 1 PUMP
SECTION
R
Select whether a system pump from a tN4
system control should operate whenever relay
1 is closed.
Note:
This item is only available when DIP switch
2 is set to tN4 System Control, the mode of
operation is set to Heat, and the Heat Source
item in the ADJUST menu is set to hydronic
(HYDr).
1
4
5
OFF, On
Default = OFF
InST
ADV
RELAY 1 PUMP DELAY
SECTION
R
Select whether a system pump is delayed from
operating whenever relay 1 is closed. The delay
allows a thermal motor zone valve to fully open.
The delay is 3 minutes.
Note:
This item is only available when DIP switch
2 is set to tN4 System Control, the mode of
operation is set to Heat, and the Heat Source
item in the ADJUST menu is set to hydronic
(HYDr).
2
6
OFF, 12:00 AM to
11:50 PM
or
OFF to 23:50
Default = OFF
ADV
RELAY 2 PUMP ON
SECTION B, F
Select the time of day at which Relay 2 turns on
for daily hot tub or pool filtration.
Note: This item is only available when a
programmable setback schedule is selected.
2
6
OFF, 0:30 to 24:00
Default = 8:00 hr
ADV
RELAY 2 PUMP RUN TIME
SECTION B, F
Select the amount of time Relay 2 should operate
for daily hot tub or pool filtration.
Note: This item is only available when a
programmable setback schedule and Relay 2
Pump On is set to a time.
2
OFF, On
Default = On
ADV
RELAY 2 SAMPLE
SECTION
B
Select whether Relay 2 must cycle the Hot Tub
pump during the unoccupied and away periods
to sample the water temperature.
Note:
This item is only available when DIP switch
2 is set to tN4 System Control and the Heat
Source item is set to hydronic (HYDr).
1
2
4
5
OFF, 1 to 12
Default = 1
ADV
SETPOINT DEVICE ENABLE
SECTION
I
Select the Setpoint Device Enable number to
allow a remote device such as a User Switch to
activate the Time Occupied override. The control
then maintains the occupied temperature for a
preset amount of time.
Note:
This item is only available when the setpoint
control has tN4 communication.
1
2
3
4
5
6
OFF, On
Default = OFF
ADV
OUTDOOR
SECTION
R
Select whether the outdoor temperature is to be
shown in the VIEW menu.
Note:
This item is only available when the control
is connected to a tN4 system and an outdoor
sensor is connected to one of the devices in the
tN4 system.
ADJUS
T MENU
Continued on next page.