beautypg.com

Naming fixtures – CommScope Redwood version 3.1 User Manual

Page 14

background image

Commissioning and Administration User Guide

13

Naming Fixtures

Each Fixture is identified by a Name and a set of data that is determined by the Gateway/Adapter

that is connected to the Fixture. When commissioning the system you can edit the Name of the

Fixture to be something more meaningful to the end-user than the default value which is the ID of

the Gateway/Adapter.

You can use different methods to name Fixtures:

Ÿ

Record the Gateway/Adapter serial number, manually find that serial number represented as

the Fixture Name and then rename it using the

button.

Ÿ

Dim each light, note the Location, and then rename it using the

button.

Ÿ

Blink a Fixture, determine which Location it is in and then rename it using the

button.

Ÿ

Use the Flashlight Naming wizard.

The most efficient and quickest method is flashlight naming.

Flashlight Naming of Fixtures

Flashlight Naming of Locations leverages the fact that each Sensor/Adapter has a light-level

sensor that will pick-up on changes of light in a given Location. You can identify and

automatically name any installed Fixture by simply shining a flashlight at the exposed Sensor

associated with that Fixture. In practice, this means you can walk into a room with unnamed

Fixtures and quickly name each without having to know anything more about the Fixture or its

Gateway/Adapter.

To name Fixtures using a flashlight:

In the Location Editor tab, create a Location named Flashlight as a child of All Locations.

1.

Drag and drop the Fixtures you want to name to the Flashlight Location.

2.

Click the Flashlight Commissioning button found at the bottom center of the screen.

3.

Note: If there are unsaved changes, the Flashlight Commissioning button is disabled.

Click the Apply button to apply the changes and then continue.

In the Flashlight Commissioning panel, assign a name and index to identify the Fixtures in a

4.

particular Location. For example, if the Fixture Name Prefix is RoomA, and the Starting
Index
is 1, the first commissioned Fixture is named RoomA001, the next is RoomA002, and
so on.