Table 15 rack 8: information, Trusted, Module t8442 – Rockwell Automation T8442 Trusted TMR Speed Monitor User Manual

Page 47

background image

Trusted

TM

Module T8442

Issue 8 Apr 10

PD-T8442

47

Ch.

Bit

Description

Detail

1

Active Module FCR B Healthy

2

Active Module FCR C Healthy

regions (slices) on the active Speed Monitor.
Healthy = 0: A slice fault has been detected
Healthy = 1: Normal

3

Active Module Ejectors Open

Active module ejectors open:
This flags the state of the active module ejectors.
Ejectors open = 0: Both front panel ejectors are closed.
Ejectors open = 1: Both front panel ejectors are open.
Note: If a single ejector changes state this flag will not change. i.e. if
both ejectors are closed and then one is opened the flag will still
report closed.

4

Standby Module FCR A
Healthy

5

Standby Module FCR B
Healthy

6

Standby Module FCR C
Healthy

Standby module FCR healthy:
These flag the health status of each of the TMR fault containment
regions (slices) on the standby Speed Monitor.
Healthy = 0: A slice fault has been detected
Healthy = 1: Normal

7

Standby Module Ejectors
Open

Standby module ejectors open:
This flags the state of the standby module ejectors.
Ejectors open = 0: Both front panel ejectors are closed.
Ejectors open = 1: Both front panel ejectors are open.
Note: If a single ejector changes state this flag will not change. i.e. if
both ejectors are closed and then one is opened the flag will still
report closed.

8 - 15

Reserved

Reserved for future use.
Bit = 0

10

-

Active module is the Primary
module

Active module is the primary module:
This indicates if the primary module is the current active module, in
the chassis and slot as defined within the OEM parameters.
1 = Secondary module is not active.
0 = Secondary module is active.

11

-

Active module is simulated

Active module is simulated:
This flags the simulated state for the active module.
Simulated = 0: The active module is not simulated
Simulated = 1: The active module is simulated.
This will only be set if the module is not present or non-operational
and the simulation enable has been set within the module
configuration in the System.ini file.

Table 15 Rack 8: Information