beautypg.com

Rack 5 line_flt (line fault integers), Table 11 rack 5: line_flt, Trusted – Rockwell Automation T8442 Trusted TMR Speed Monitor User Manual

Page 39: Module t8442

background image

Trusted

TM

Module T8442

Issue 8 Apr 10

PD-T8442

39

3.2.5.

Rack 5 LINE_FLT (Line Fault Integers)

Ch.

Channel Description

Detail

1

Group 1, Channel 1, Input line fault

2

Group 1, Channel 2, Input line fault

3

Group 1, Channel 3, Input line fault

4

Group 2, Channel 1, Input line fault

5

Group 2, Channel 2, Input line fault

6

Group 2, Channel 3, Input line fault

7

Group 3, Channel 1, Input line fault

8

Group 3, Channel 2, Input line fault

9

Group 3, Channel 3, Input line fault

Input Line Fault:
Asserted TRUE by the System Main Processor if a speed
monitor input reports a line fault (State 3) in Rack 4,
channels 1 through 9. State 3 is determined by an
algorithm that monitors the input dynamically.
Line Fault Input = 0: Normal
Line Fault Input = 1: Line fault

10

Group 1, Over-speed coil line fault

11

Group 1, Over-acceleration coil line fault

12

Group 2, Over-speed coil line fault

13

Group 2, Over-acceleration coil line fault

14

Group 3, Over-speed coil line fault

15

Group 3, Over-acceleration coil line fault

Coil Line Fault:
Asserted by the System Main Processor if a speed
monitor coil drive output reports a fault (All states except 2
& 4) in Rack 4, channels 10 through 15.
Coil line fault = 0: Normal
Coil line fault = 1: Line fault

16

17

18

19

20

21

Reserved

Reserved for future use.

Table 11 Rack 5: LINE_FLT