3.2.5.
Rack 5 LINE_FLT (Line Fault Integers)
Ch.
Channel Description
Detail
1
Group 1, Channel 1, Input line fault
2
Group 1, Channel 2, Input line fault
3
Group 1, Channel 3, Input line fault
4
Group 2, Channel 1, Input line fault
5
Group 2, Channel 2, Input line fault
6
Group 2, Channel 3, Input line fault
7
Group 3, Channel 1, Input line fault
8
Group 3, Channel 2, Input line fault
9
Group 3, Channel 3, Input line fault
Input Line Fault:
Asserted TRUE by the System Main Processor if a speed
monitor input reports a line fault (State 3) in Rack 4,
channels 1 through 9. State 3 is determined by an
algorithm that monitors the input dynamically.
Line Fault Input = 0: Normal
Line Fault Input = 1: Line fault
10
Group 1, Over-speed coil line fault
11
Group 1, Over-acceleration coil line fault
12
Group 2, Over-speed coil line fault
13
Group 2, Over-acceleration coil line fault
14
Group 3, Over-speed coil line fault
15
Group 3, Over-acceleration coil line fault
Coil Line Fault:
Asserted by the System Main Processor if a speed
monitor coil drive output reports a fault (All states except 2
& 4) in Rack 4, channels 10 through 15.
Coil line fault = 0: Normal
Coil line fault = 1: Line fault
16
17
18
19
20
21
Reserved
Reserved for future use.
Table 11 Rack 5: LINE_FLT