Rack 8 info (information integers), Trusted, Module t8442 – Rockwell Automation T8442 Trusted TMR Speed Monitor User Manual
Page 46
Trusted
TM
Module T8442
Issue 8 Apr 10
PD-T8442
46
3.2.9.
Rack 8 INFO (Information Integers)
Ch.
Bit
Description
Detail
1
-
Active module chassis number Active module chassis number:
This indicates the chassis location of the currently active Speed
Monitor.
2
-
Active module slot number
Active module slot number:
This indicates the slot location within the chassis of the currently
active Speed Monitor.
This value will dynamically change on active/standby module
changeover to reflect the change in active/standby module location.
3
-
Active module healthy
Active module healthy:
This indicates the health status of the active Speed Monitor.
Healthy = 0: A fault has been detected
Healthy = 1: Normal
4
-
Active module state
Active module state:
This indicates the current operating mode of the active Speed
Monitor.
State = 0: Unknown, Module not present or offline.
State = 1: Configuration mode
State = 2: Standby mode
State = 3: Active mode
State = 4: Maintain mode
State = 5: Shutdown mode
This would normally indicate state 3, although other states may be
indicated on module initialisation and during an active/standby
changeover.
All other states are invalid.
5
-
Standby module chassis
number
Standby module chassis number:
This indicates the chassis location of the standby Speed Monitor.
6
-
Standby module slot number
Standby module slot number:
This indicates the slot location within the chassis of the standby
Speed Monitor.
This value will dynamically change on active/standby module
changeover to reflect the change in active/standby module location.
7
-
Standby module healthy
Standby module healthy:
This indicates the health status of the standby Speed Monitor.
Healthy = 0: A fault has been detected
Healthy = 1: Normal
8
-
Standby module state
Standby module state:
This indicates the current operating mode of the standby Speed
Monitor.
State = 0: Unknown, Module not present or offline.
State = 1: Configuration mode
State = 2: Standby mode
State = 3: Active mode
State = 4: Maintain mode
State = 5: Shutdown mode
All other states are invalid.
This would normally indicate state 2, although other states may be
indicated on module initialisation and during an active/standby
changeover.
9
0
Active Module FCR A Healthy
Active module FCR healthy:
These flag the health status of each of the TMR fault containment