3.2.4.

Rack 4 STATE (State Integers)

Ch. Channel Description

Detail

1

Group 1, Channel 1, Input State

2

Group 1, Channel 2, Input State

3

Group 1, Channel 3, Input State

4

Group 2, Channel 1, Input State

5

Group 2, Channel 2, Input State

6

Group 2, Channel 3, Input State

7

Group 3, Channel 1, Input State

8

Group 3, Channel 2, Input State

9

Group 3, Channel 3, Input State

Input State:
The digital input state for each of the sensor inputs.
State = 0: State invalid
State = 1: DC low (gear valley)
State = 2: DC high (gear tooth)
State = 3: Sensor fault (channel discrepancy)
State = 4: Normal operating speed range
State = 5: Over-Acceleration trip threshold exceeded
State = 6: Over-Speed trip threshold exceeded
State = 7: Faulted or state unknown
Note:
State 1 and State 2 will only be reported when no new
tooth data is received within 3 seconds. i.e. If at least one
tooth is detected every three seconds then the channel will
be reported as NORMAL State 4.
State 3 will be reported while the input is discrepant unless
the time exceeds the configured Discrepancy Duration
Limit (see 3.1.10) at which point the channel will be
declared as faulted and state 7 will be reported.

10

Group 1, Over-speed coil drive state

11

Group 1, Over-acceleration coil drive state

12

Group 2, Over-speed coil drive state

13

Group 2, Over-acceleration coil drive state

14

Group 3, Over-speed coil drive state

15

Group 3, Over-acceleration coil drive state

Coil Drive State:
The digital output state for each of the coil drive outputs.
Coil Drive State = 0: Invalid
Coil Drive State = 1: No Coil Vfield
Coil Drive State = 2: Coil de-energized
Coil Drive State = 3: Load contacts not connected
Coil Drive State = 4: Coil energized
Coil Drive State = 5: Not used
Coil Drive State = 6: Field Fault. Current is detected when
there should be none, or no current is flowing when there
should be.
Coil Drive State = 7: Faulted or state unknown
Note that there are 4 coils for each output channel. The
reported state reflects the summary state of all the coils
associated with the given channel

16

Group 1, Over-speed trip state

17

Group 1, Over-acceleration trip state

18

Group 2, Over-speed trip state

19

Group 2, Over-acceleration trip state

20

Group 3, Over-speed trip state

21

Group 3, Over-acceleration trip state

Trip State:
The output trip state for each of the output channels.
Trip State = 2: Channel Tripped
Trip State = 4: Channel Not Tripped
All other states are invalid.

22

Group 1, Over-speed test state

23

Group 2, Over-speed test state

24

Group 3, Over-speed test state

Over-speed test state:
Reports if the group over-speed test is still in effect or has
expired due to a timeout, trip, or reset.
Test State = 0: Not in test mode
Test State = 1: Test mode is active
All other states are invalid.