beautypg.com

Table 14 specific diagnostic error codes, Trusted, Module t8442 – Rockwell Automation T8442 Trusted TMR Speed Monitor User Manual

Page 45

background image

Trusted

TM

Module T8442

Issue 8 Apr 10

PD-T8442

45

0x6Cmn

Qd

0-3

Op

0-5

SFIU_RELAY_DRIVE_XTALK_FAUL
T

Crosstalk between relay commands, or DIAGs

0x6Cmn

4+
(Qd

0-3)

Op

0-5

SFIU_RELAY_IMON_XTALK_FAULT

Crosstalk between relay IMONs

0x6D0n

Op

0-5

SFIU_IMON_QUAD_DISCREP
(LEG1)

IMON Leg1 Q1-Q2 Discrepancy

0x6D1n

Op

0-5

SFIU_IMON_QUAD_DISCREP
(LEG2)

IMON Leg2 Q1-Q2 Discrepancy

0x6D3n

Op

0-5

SFIU_RLY_IMON_LEG_DISCREP

IMON Leg to Leg Imbalance

0x6E0n

Gp

0-2

SFIU_VMON_QUAD_DISCREP
(24V1)

24V1 Q1-Q2 Discrepancy

0x6E1n

Gp

0-2

SFIU_VMON_QUAD_DISCREP
(24V2)

24V2 Q1-Q2 Discrepancy

0x6E2n

Gp

0-2

SFIU_VMON_QUAD_DISCREP
(15V1)

15V1 Q1-Q2 Discrepancy

0x6E3n

Gp

0-2

SFIU_VMON_QUAD_DISCREP
(15V1)

15V2 Q1-Q2 Discrepancy

0x6F0n

Gp

0-2

SFIU_CONTACT_QUAD_DISCREP

Relay Contact Q1-Q2 Discrepancy

Table 14 Specific Diagnostic Error Codes