Invalid configuration errors – Rockwell Automation 1440-VLF02-01RA XM-121 Absolute Shaft Module User Manual
Page 92
![background image](/manuals/581439/92/background.png)
Publication GMSI10-UM014D-EN-P - May 2010
84 DeviceNet Information
Example
To save the configuration parameters to the non-volatile memory (EEPROM),
fill in the Class Instance Editor as shown below.
Invalid Configuration Errors
A Start or Save service request to an XM module may return an Invalid Device
Configuration error when there is a conflict amongst the configuration
settings.
The general error code for the Invalid Device Configuration error is D0
hex
.
An additional error code is returned with the general error code to specify
which configuration settings are invalid. The table below lists the additional
error codes associated with the Invalid Device Configuration error.
Select the Save
service code
Clear Send the attribute
ID and then enter the
Class (320
hex
) and
Instance (1)
Click Execute to
initiate the
action
Additional Error Codes returned with the Invalid Device Configuration Error (0xD0)
Error Code
(Hex)
Description
01
No specific error information is available.
02
Mismatched transducer, channel, and/or measurement unit.
03
Inverted transducer fault high/low values.
04
Alarm thresholds conflict with the alarm condition.
05
Alarm speed range is invalid.
06
Band minimum frequency is greater than maximum frequency. Or,
maximum frequency is greater than FMAX.
07
Relay is associated with an alarm that is not enabled.
08
Tachometer must be enabled for alarm or channel settings.
09
A senseless speed range is enabled on a speed alarm.