Identity object (class id 01h), Class attributes, Instance attributes – Rockwell Automation 1440-VLF02-01RA XM-121 Absolute Shaft Module User Manual
Page 100: Status, Class attributes instance attributes status, Identity object (class id 01, Instance attributes status
Publication GMSI10-UM014D-EN-P - May 2010
92 DeviceNet Objects
Identity Object
(Class ID 01
H
)
The Identity Object provides identification and general information about the
device.
Class Attributes
The Identity Object provides no class attributes.
Instance Attributes
Status
The Status is a 16 bit value. The following bits are implemented.
Table C.1 Identity Object Instance Attributes
Attr ID
Access
Rule
Name
Data Type
Default Value
1
Get
Vendor ID
UINT
668 = Entek
2
Get
Device Type
UINT
109 (Specialty I/O)
3
Get
Product Code
UINT
38 (0x26)
4
Get Revision:
Major
Minor
STRUCT OF
USINT
USINT
Value varies with each firmware revision.
Value varies with each firmware revision.
5
Get
Status
WORD
6
Get
Serial Number
UDINT
7
Get Product
Name
SHORT_
STRING
"XM-121 Absolute Shaft Module"
Table C.2 Identity Object Status
Bit
Name
Description
0
Owned
TRUE indicates that the module has an owner. More
specifically, the Predefined Master/Slave Connection Set
has been allocated to a master.
1
Reserved, set to 0
2
Configured
This bit is set whenever a saved configuration is
successfully loaded from non-volatile memory. This bit is
cleared whenever the default configuration is restored or
loaded.
3