Publication GMSI10-UM014D-EN-P - May 2010
DeviceNet Objects 113
1
This attribute is read-only for instance 1. The instance 1 setting is based upon the instance 2 setting. If the
Channel 2 Output Data Units are English, then the Channel 1 Output Data Units will be mils. If the Channel 2
Output Data Units are Metric, then the Channel 1 Output Data Units will be µm.
2
This attribute cannot be set for instance 2. The instance 2 setting matches the channel 1 setting.
10
Get/Set
Full Scale
REAL
The maximum signal
expected to be processed
by the channel.
Volts peak
Setting the Full Scale to a
greater value allows the
channel to handle greater input
signals without saturating or
clipping. Setting the Full Scale
to a lesser value allows the
signal to be measured with
greater resolution.
100
Get
Very Low HPF
Corner
Frequency
REAL
The frequency, in Hz, of
the "Very low" Low
Cutoff Frequency option
for attribute 5.
Hz
101
Get
Low HPF Corner
Frequency
REAL
The frequency, in Hz, of
the "Low" Low Cutoff
Frequency option for
attribute 5.
Hz
102
Get
Medium HPF
Corner
Frequency
REAL
The frequency, in Hz, of
the "Medium" Low
Cutoff Frequency (low
frequency corner) option
for attribute 5.
Hz
103
Get
High HPF Corner
Frequency
REAL
The frequency, in Hz, of
the "High" Low Cutoff
Frequency option for
attribute 5.
Hz
104
Get
Very High HPF
Corner
Frequency
REAL
The frequency, in Hz, of
the "Very high" Low
Cutoff Frequency option
for attribute 5.
Hz
Table C.31 Channel Object Instance Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics