Instance attributes – Rockwell Automation 1440-VLF02-01RA XM-121 Absolute Shaft Module User Manual
Page 137

Publication GMSI10-UM014D-EN-P - May 2010
DeviceNet Objects 129
Instance Attributes
Table C.54 Transducer Object Instance Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics
3
Get
DC Bias
REAL
The measured average DC
bias of the transducer
signal in volts.
Volts
4
Get
Status
BOOL
Indicates whether a
transducer fault exists
(the measured DC Bias is
outside the range
specified by Fault High
and Low).
0 = No fault
1 = A transducer fault exists
5
Get/Set
Sensitivity
Value
REAL
Value of the sensitivity of
the transducer in
millivolts per Sensitivity
Units.
6
Get/Set
Sensitivity Units ENGUNIT
Units of the denominator
of the Sensitivity Value.
See DeviceNet Specification
Volume 1 Appendix K.
Valid values:
Channel 1
mils = 0800 hex
µm = 2204 hex
Channel 2
g =1504 hex
in/sec = 2B07 hex
mils = 0800 hex
mm/s = 0900 hex
Channel 3
Not applicable
7
Get/Set
Fault High
REAL
The maximum expected
DC Bias voltage from the
transducer in volts.
Volts
8
Get/Set
Fault Low
REAL
The minimum expected
DC Bias voltage from the
transducer in volts.
Volts
9
Get/Set
Power Type
USINT
Indicates the type of
power supplied to the
transducer.
0 = No power supplied
1 = Constant current (IEPE
accelerometer)
13
Get/Set
DC Bias Time
Constant
REAL
The time constant value
used for exponential
averaging of the DC Bias
value (a low pass
filter/output smoothing
filter).
Seconds