Of the most important, Tab. 2.3-1, Provides a su – Rockwell Automation Low-Voltage Switchgear and Controlgear User Manual
Page 34
![background image](/manuals/581225/34/background.png)
Parameter
Details chapter
Discon
n
ec
to
rs
Fuses
Circuit br
eak
-
ers
Load switch
es
Con
tac
tor
Starters
Rated isolation voltage U
i
P P P P P
Rated operational voltage U
e
(<U
i
)
P P P P P
Rated impulse withstand voltage U
imp
P P P P
Rated operational current I
e
P P P P P
Utilization category
P P P P
Short-circuit withstand capacity / short-circuit
protection
P P P
Rated short-circuit making capacity I
cm
P
P
Rated short-circuit breaking capacity I
cu
, I
cs
P P
Cut-off current
C C
Let-through energy (Joule integral)
C C
Rated short time current I
cw
C C C
Short-circuit coordination
(Type 1, Type 2) with fuses or circuit breakers
P
Thermal load
P P P P
Ambient temperature
C C C C C
Operational overcurrents
(for example heavy-duty starting)
C C C C C
Life span
C
C
Frequency of operation
C
C
Rated frequency / harmonics
C C C C C
Safety clearances
P P P
Mounting position
C C
Pollution degree
A A A A A
Overvoltage category
A A A A A
Protective separation
A A A A A
Site altitude
A A A A A
Shock and vibration
A A A A A
Humidity / climatic loading
A A A A A
Chemical ambient influences
A A A A A
Radioactive radiation
A A A A A
UV radiation
A A A A A
External form / IP degree of protection
A A A A A
Tab. 2.3-1
Selection criteria for low-voltage switchgear for main circuits
P … Primary selection factors
C … Complementary selection factors
A … Additional criteria
LVSAM-WP001A-EN-P - April 2009