Installing PanelView 1000e Terminals
Publication 2711E-821 – January 1998
Backlight Intensity
You can adjust the terminal display intensity while in Configure
mode. For details on how to increase or decrease terminal display
intensity, see Chapter 5, Configuring PanelView Operator Terminals,
in this manual. The terminal display is initially set at the maximum
intensity.
Connecting Power to the Terminal
The power requirements for the terminal are 115 Vac (60 Hz) or
230 Vac (50 Hz).
Before connecting the power cable to the power connector at the
bottom of the terminal, make sure the cable is not carrying power.
Because the terminal has no power switch, connecting the ac power
will start the terminal if power is present in the cable.
!
ATTENTION: Be sure to connect the wire to Ground
(GND) on the power connector. Failure to do so could
result in electrical hazard to the operator (and damage
to the equipment).
To connect power to the terminal:
1. Prepare the power wires by stripping the wire of its protective
coating to a length of
½ to ¾ of an inch (1 to 2 cm).
2. Turn the screw on the power connector counterclockwise to open
the wire slot. Insert the wire fully into its appropriate slot.
3. Turn the screw clockwise until the wire is held firmly in place.
4. Repeat the procedure until all three power wires are connected.
Figure 2.10 The Power Connector
20164
L1 ~ (Vac)
L2N ~ (Vac)
L1
L2
GND
(Protective Earth)