Ac power, Fuses, Character set – Rockwell Automation 2711E-xxxx PanelView Operator Terminals User Manual User Manual
Page 168: User memory

Specifications: 1400e Operator Terminal
C–7
Publication 2711E-821 – January 1998
Following are the ac power specifications for the PanelView 1400e
terminal.
Power Supply Type
Switching
Range
90–132, 180–264 V ac
automatic setting by the PanelView 1400e terminal to
match available power supply
Frequency Range
47–63 Hz
Power Consumption
Color terminal
75 W typical
100 W maximum
Volt Amps
Color terminal
180 VA typical
240 VA maximum
While the color terminal degausses, there is a 5.5-amp surge at
115 volts. At 230 V, there is an 11-amp surge that lasts less than
400 milliseconds. Automatic degauss occurs every time ac power is
re-applied to the terminal.
PanelView 1400e terminals:
•
Require one fuse for each ac line
•
Have fuses the user can access from the rear of the terminal
•
Accepts the following fuse type: BUSS GDC-3.15, 3.15 A,
250 V ac, 5 mm x 20 mm
!
ATTENTION: Fuses must be replaced by authorized
service personnel only. PanelView 1400e terminals
contain neutral fuses. Disconnect power before
servicing the unit.
PanelView 1400e terminals support the IBM character set for alarm,
local, and information messages.
PanelView 1400e terminals support:
•
256K bytes of Flash memory for application file
•
PCMCIA card slot of variable size (depends on user application
file)
RAM tests and Memory Checksum tests can be initiated in the
Terminal Diagnostics screen in Configuration mode.
AC Power
Fuses
Character Set
User Memory