Troubleshoot the System Chapter 6
Communication
8
Communication Server Error
Contact technical support providing this data.
ID1-/*S:0 Param1*/, ID2-/*S:0 Param2*/, P1-/*S:0
Param3*/, P2-/*S:0 Param4*/, P3-/*S:0 Param5*/,
P4-/*S:0 Param6*/, P5-/*S:0 Param7*/, P6-/*S:0
Param8*/
Reboot the terminal.
Communication
9
Communication Server Error
Contact technical support providing this data.
ID1-/*S:0 Param1*/, ID2-/*S:0 Param2*/
Reboot the terminal.
Communication
10
Write Error for Alias /*S:0 Param2*/, Controller
/*S:0 Param3*/, Address is /*S:0 Param4*/,
Communication Flag is /*S:0 Param1*/
The terminal is having trouble writing the external
tag at this controller and address.
Verify you have good communication to the
controller.
Verify that the communication network cable is
connected.
If new ladder logic is downloading to the controller,
you could see this message. After the download,
communication should run normally.
If a remote device not responding alert is present,
then all external tags being written to will generate
this alert.
Is the address configured in the controller? If the
address is configured as read only at the controller,
this address can not be written to. Set this external
tag as read and remove panel devices from your
application that can write data to this external tag.
Communication
11
Read Error for Alias /*S:0 Param2*/, Controller
/*S:0 Param3*/, Address is /*S:0 Param4*/,
Communication Flag is /*S:0 Param1*/
The terminal is having trouble reading the
external tag at this controller and address.
Verify you have good communication to the
controller.
Verify that the communication network cable is
connected.
If new ladder logic is downloading to the controller,
you could see this message. After the download,
communication should run normally.
If a remote device not responding alert was present,
then all external tags being read from will generate
this alert.
Is the address configured in the controller? If the
address is configured as write only at the controller,
this address can not be read from. Set this external
tag as write and remove panel devices from your
application that can read data from this external
tag.