How to configure a trigger, How to configure a trigger -3 – Rockwell Automation 9220-WINTA ControlNet Traffic Analyzer Reference Manual User Manual
Page 37
Publication 9220-052C-EN-P - August 2002
Triggers and Filters 4-3
How to Configure a Trigger
When you choose to start or stop a trigger on a condition, a trigger list
area appears. You can add, edit, or delete conditions in this list area
by clicking the right mouse button. A pop-up menu appears.
When you add or edit a trigger condition, you see the following box:
TIP
Another way you can add, edit, or delete a trigger condition is
by pressing the Insert, Enter, or Delete key, respectively.
Define the Producer MAC ID(s) you want to trigger. You can define:
•
a single Producer MAC ID (in a range 0-255).
•
a group of IDs. Separate the range by a hyphen (2-88). The range can extended from 0 to 255.
•
multiple IDs. Separate the IDs by a semi-colon (2;9;27) a group and multiple IDs (2-7;3;8).
If you do not enter a value in this field, the full range (0-255) becomes the default value.
Define the Producer MAC ID(s) you want to trigger in each LPacket.
•
For a Generic LPacket, it is the Producer/Consumer ID.
•
For a Fixed LPacket, it is the Destination ID.
•
For a Broadcast ID, it is 255.
You can define:
•
a single Producer/Consumer MAC ID (in a range 0-255).
•
a group of IDs. Separate the range by a hyphen (2-88).
The range can extended from 0 to 255.
•
multiple IDs. Separate the IDs by a semi-colon (2;9;27).
•
a group and multiple IDs (2-7;3;8).