Appendix B Expansion I/O Data Mapping

2085-IRT4 Status Data Mapping

Word

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Status 0

DE3

DE2

DE1

DE0

OC3

OC2

OC1

OC0

R3

R2

R1

R0

S3

S2

S1

S0

Status 1

O3

O2

O1

O0

U3

U2

U1

U0

T3

T2

T1

T0

CJC
over

CJC
under

CJC
OC

CJC
DE

Status 2

PU

GF

CRC

Reserved

Field Descriptions for 2085-IRT4

Field

Description

CJC OC

Cold Junction
Compensation
Open Circuit

Indicates that the cold junction sensor is open-circuit. CJC DE
bit, when set, indicates the cold junction sensor current
readings is not reliable. The previous reading shall be used
instead. It indicates internal compensation status if Tx is set.

CJC DE

Cold Junction
Compensation
Data Error

Indicates that the cold junction sensor current readings is not
reliable. The previous reading will be used instead. It indicates
internal compensation status if Tx is set.

CJC over

Cold Junction
Compensation
overrange

Indicates cold junction sensor overrange (above 75 °C).

CJC under

Cold Junction
Compensation
underrange

Indicates cold junction sensor is underrange (below -25 °C).

CRC

CRC error

Indicates there is a CRC error on data receive. All channelfault
bits (Sx) are also set. The error is cleared when the next
good data is received.

DEx

Data Error

Indicates that the current input data is not reliable. The
previous input data is sent to the controller instead. Diagnostic
status bits are for internal use only.

GF

General Fault

Indicates a fault has occurred, including: RAM test failure, ROM
test failure, EEPROM failure, and reserved bits. All channel
fault bits (Sx) are also set.

OCx

Open-Circuit Flag

Indicates that an open-circuit condition exists on the channel x.

Ox

Over-Range Flag

Indicates the controller is attempting to drive the analog output
above its normal operating range or above the channel's High
Clamp level. However the module continues to convert analog
output data to a maximum full range value if clamp levels are
not set for the channel.

PU

Power Up

Indicates an unexpected MCU reset has occurred in RUN mode.
All channel error bits (Ex) and fault bits (Sx) are also set. The
module stays connected with no configuration after the reset.
PU and channel fault bits are cleared when a good
configuration is downloaded.

Rx

RTD compensation

Indicates that the RTD compensation of channel x is not
working. This is effective for RTD and ohm type only.