2085-IRT4

For the RTD and Thermocouple expansion I/O, 2085-IRT4, you can configure
sensor type, data format, temperature units, and other properties, on each of the
four individual channels.

Configuration Parameters for 2085-IRT4

Configuration Property

What to do

Description

Enable channel

Click the box to enable.

This parameter enables the particular
channel for operation.

Sensor Type

Select from the following
sensors:

100

Ω Platinum 385

200

Ω Platinum 385

100

Ω Platinum 3916

200

Ω Platinum 3916

100

Ω Nickel 618

200

Ω Nickel 618

120

Ω Nickel 672

100

Ω Copper 427

0…500 Ohm

0…100 mV

Thermocouple B

Thermocouple C

Thermocouple E

Thermocouple J

Thermocouple K

Thermocouple TXK/XK (L)

Thermocouple N

Thermocouple R

Thermocouple S

Thermocouple T

Defines the RTD or Thermocouple sensor
type for the channel.