Output specifications – 2085-ov16 and 2085-ob16 – Rockwell Automation 2085 Micro800 Discrete and Analog Expansion I/O Modules User Manual
Page 55

Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
47
Specifications Appendix A
2085-OV16 Sink and 2085-OB16 Source DC Output Module
Attribute
2085-OV16
2085-OB16
Number of outputs
16 sinking
16 sourcing
Dimensions, HxWxD
44.5 x 90 x 87 mm
(1.75 x 3.54 x 3.42 in.)
Shipping weight,
approx.
220 g (7.76 oz)
Bus current draw,
max
200 mA @ 5V DC
Wire size
Wiring category
(1)
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring
and Grounding Guidelines, publication
2 – on signal ports
Terminal screw
torque, max
0.5…0.6 Nm
(4.4…5.3 lb-in.)
(2)
(2) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.
Output circuit type
24V DC sink
24V DC source
Power dissipation,
total
5 W
Power supply
24V DC, Class 2
Status indicators
16 Yellow channel indicators
Isolation voltage
50V (continuous), Reinforced Insulation Type, channel to system
Type tested @ 720V AC for 60 s
Enclosure type
rating
Meets IP20
North American
temp code
T4
Output Specifications – 2085-OV16 and 2085-OB16
Attribute
2085-OV16
2085-OB16
Operating voltage range
10…30V DC
On-state voltage, min
10V DC
On-state voltage, nom
24V DC
On-state voltage, max
30V DC
On-state current, max
0.5 A @ 30V DC, per output
8 A, per module
On-state voltage drop, max
1.0V DC @ 0.5 A
Off-state leakage current, max
1 mA @ 30V DC
Min
Max
Solid
0.34 mm
2
(22 AWG)
2.5 mm
2
(14 AWG)
Copper wire rated @ 90 °C (194
°F), or greater, 1.2 mm
(3/64 in.) insulation max
Stranded
0.20 mm
2
2.5 mm
2
(14 AWG)