Rockwell Automation Publication 2080-UM003A-EN-E - March 2013

Chapter 5 Configure Your Expansion I/O Module

Units

Set as °C or °F

Sets the temperature unit to be used by
the channel.

RTD Wiring Type

Set as any of the following:

2-wire

3-wire

4-wire

The wiring type for channel x.
This parameter is only available when the
Sensor Type for the channel is RTD or (0
to 500 Ohm).

RTD 2Wire Cable
Resistance

Replace value from 0.0
ohms…500.00 ohms to
0.0 ohms…655.35 ohms.

The specified cable resistance for the
2-wire cable. When the RTD 2Wire Cable
Resistance value is smaller than the input
value, it is subtracted from the input
value during each read. When the value
is greater than the input value, the
under-range or open status bit is set (1).
To configure the wire resistance, the
Sensor Type must be RTD or (0…500
Ohm) and the RTD Wiring Type must be
2-wire.
Otherwise, this parameter is not
available.

Data Format

Choose from the following
options:

Raw/Proportional Data

Engineering Units*1

Engineering Units*10

Percent range

For more information, see:

Data format on page 12

Valid Range of the Data Formats for
2085-IRT4 on page 12

Configuration Parameters for 2085-IRT4

Configuration Property

What to do