Input specifications – 2005-ia8 and 2085-im8 – Rockwell Automation 2085 Micro800 Discrete and Analog Expansion I/O Modules User Manual
Page 56
48
Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Appendix A Specifications
2085-IA8, 2085-IM8, 2085-OA8 AC Input/Output Modules
Attribute
2085-IA8
2085-IM8
2085-OA8
Number of I/O
8
Dimensions, HxWxD
28 x 90 x 87 mm
(1.10 x 3.54 x 3.42 in.)
Shipping weight,
approx.
140 g (4.93 oz)
Bus current draw, max
5V DC, 150 mA
5V DC, 180 mA
Wire size
Insulation stripping
length
10 mm (0.39 in.)
Wiring category
(1)
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring
and Grounding Guidelines, publication
.
2 – on signal ports
Wire type
Copper
Terminal screw torque,
max
0.5…0.6 Nm
(4.4…5.3 lb-in.)
(2)
(2) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.
Input/output circuit
type
120V AC input
240V AC input
120V/240V AC output
Power supply
120V AC, 50/60 Hz
240V AC, 50/60 Hz
120V/240V AC,
50/60 Hz
Power dissipation,
total
2.36 W
2.34 W
5.19 W
Enclosure type rating
Meets IP20
Status indicators
8 yellow indicators
Isolation voltage
150V (continuous),
Reinforced Insulation
Type, channel to
system
Type tested @ 1950V
DC for 60 s
240V (continuous), Reinforced Insulation Type,
channel to system
Type tested @ 3250V DC for 60 s
North American temp
code
T4
Input Specifications – 2005-IA8 and 2085-IM8
Attribute
2085-IA8
2085-IM8
Number of Inputs
8
Voltage category
120V AC
240V AC
Operating voltage range
74…120V AC, 50/60 Hz
159…240V AC, 50/60 Hz
Off-state voltage, max
20V AC
40V AC
Min
Max
Solid
0.34 mm
2
(22 AWG)
2.5 mm
2
(14 AWG)
Copper wire rated @ 90 °C
(194 °F), or greater,
1.2 mm
(3/64 in.) insulation max
Stranded
0.20 mm
2
2.5 mm
2
(14 AWG)