Derating curve for 2085-iq16, Derating curve for 2085-iq32t – Rockwell Automation 2085 Micro800 Discrete and Analog Expansion I/O Modules User Manual
Page 54
![background image](/manuals/580122/54/background.png)
46
Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Appendix A Specifications
Derating Curve for 2085-IQ16
Derating Curve for 2085-IQ32T
Status indicators
16 yellow indicators
32 yellow indicators
Isolation voltage
50V (continuous), Reinforced Insulation Type, channel to system
Type tested @ 720V DC for 60 s
Enclosure type rating
Meets IP20
North American temp
code
T4
Operating voltage
range
10…30V DC, Class 2
21.6…26.4V AC, 50/60 Hz, Class 2
See
and
Derating Curve for 2085-IQ32T on
Off-state voltage, max
5V DC
Off-state current, max
1.5 mA
1.2 mA
On-state current, min
1.8 mA @ 10V DC
On-state current, nom
6.0 mA @ 24V DC
5.2 mA @ 24V DC
On-state current, max
8.0 mA @ 30V DC
7.0 mA @ 30V DC
Input impedance, max
3.9 k
Ω
4.6 k
Ω
IEC input compatibility
Type 3
Type 1
(1) Meets IEC Type 1 24V DC Input Specifications.
(2) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring
and Grounding Guidelines, publication
.
(3) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.
2085-IQ16 and 2085-IQ32T DC Sink/Source Input Modules
(1)
Attribute
2085-IQ16
2085-IQ32T
30
26.4
30
°C
65
°C
Input voltage (V)
45302
Temp
30
26.4
32
24
30
°C
65
°C
18
24
Input voltage (V)
45301
Number
of inputs