2085-iq16 and 2085-iq32t – Rockwell Automation 2085 Micro800 Discrete and Analog Expansion I/O Modules User Manual

Page 43

background image

Rockwell Automation Publication 2080-UM003A-EN-E - March 2013

35

Configure Your Expansion I/O Module Chapter 5

2085-IQ16 and 2085-IQ32T

For the 16- and 32-channel DC input modules, 2085-IQ16 and 2085-IQ32T
respectively, you can configure OFF to ON and ON to OFF ranges.

2085-OV16, 2085-OB16, 2085-OW16, 2085-OA8, 2085-OW8

The output modules, 2085-OV16, 2085-OB16, 2085-OW16, 2085-OA8,
2085-OW8, only have device details available to the user in Connected
Components Workbench. There are no user configuration pages for these
modules in the Connected Components Workbench software.

High High Alarm

Check the checkbox to enable
an alarm. By default, High
High and Low Low Alarms
are disabled and High and
Low alarms are enabled.

Process level alarms alert you when the
module has exceeded configured high, high
high, low, and low low limits for each
channel.

High Alarm

Low Alarm

Low Low Alarm

Configuration
Property

What to do

Input

OFF to ON

Choose from the following values:
8.0 ms
4.0 ms
2.0 ms (default)
1.0 ms
0.5 ms
0.1 ms
0.0 ms

ON to OFF

Choose from the following values:
8.0 ms (default)
4.0 ms
2.0 ms
1.0 ms
0.5 ms
0.1 ms
0.0 ms

Configuration Parameters for 2085-IF4 and 2085-IF8

Configuration
Property

What to do

Description