Preface – Rockwell Automation 9323-PA2E APS SLC 500 Import/Export Utility User Manual User Manual
Page 98
Preface
APS Import/Export Utility User Manual
A-12
Instruction
Description
Parameter
Valid Addressing
Mode(s)
Valid File Types
Immediate
Values
LN
➁
Natural Log
source
direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
-32,768-32,767
fĆmin-fĆmax
destination
direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
none
LOG
➁
Log to the Base 10
source
direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
-32,768-32,767
fĆmin-fĆmax
destination
direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
none
MCR
Master Control Relay
none
MEQ
Mask Compare Equal
To
source
direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, A, ST, M
none
source mask
direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, A, ST, M
-32,768-32,767
compare
direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, A, ST, M
-32,768-32,767
MOV
Move
source
direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
-32,768-32,767
fĆmin-fĆmax
destination
direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
none
MSG
(5/02 only)
Message
read/write
0=read,1=write
(5/02 only)
target device
2=500CPU,
4=485CIF
control block
direct
N
none
control block length
7
local address
direct
O, I, S, B, T, C, R,
N, A
none
target node
0-31
target address
direct
O, I, S, B, T, C, R,
N, A
0-255
message length
T, C, R
1-13
I, O, S, B, N
1-41
➁ Supported only by SLC 5/03 OS302 and SLC 5/04 OS401 processors.