Preface – Rockwell Automation 9323-PA2E APS SLC 500 Import/Export Utility User Manual User Manual
Page 104

Preface
APS Import/Export Utility User Manual
A-18
Instruction
Description
Parameter
Valid Addressing
Mode(s)
Valid File Types
Immediate
Values
SQO
Sequencer Output
file
indexed direct
indexed indirect
O, I, S, B, N, A, ST none
mask
direct, indexed direct
➄
indirect, indexed indirect
O, I, S, B, T, C, R,
N, A, ST, M
-32,768-32,767
destination
direct, indexed direct
➄
indirect, indexed indirect
O, I, S, B, T, C, R,
N, A, ST, M
none
control
direct
R
none
length
1-255
position
0-255
SQR
➃
Square Root
source
direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
-32,768-32,767
fĆmin-fĆmax
destination
direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
none
STD
➃
Selectable Timed
Interrupt Disable
none
STE
➃
Selectable Timed
Interrupt Enable
none
STS
➃
Selectable Timed
Interrupt Start
file
direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, A, ST, M
0, 3-255 except
MicroLogix 1000
controllers
always equal 5
time
direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, A, ST, M
0-255 (SLC 5/02
and MicroLogix
1000), 0-32,767
(SLC 5/03 and
5/04)
SUB
Subtract
source A
direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
-32,768-32,76
fĆmin-fĆmax
source B
direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
-32,768-32,767
fĆmin-fĆmax
destination
direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
none
➃ Supported only by SLC 5/02, SLC 5/03, and SLC 5/04 processors and MicroLogix 1000 controllers.