beautypg.com

Specifications, Scanner operating specifications, Network specifications – Rockwell Automation 1747-SN Remote I/O Scanner User Manual

Page 97: Appendix a, Appendix

background image

1

Publication 1747-UM013B-EN-P - January 2005

Appendix

A

Specifications

This appendix provides scanner and system specifications, as well as
throughput information. Topics include:

• scanner operating specifications
• network specifications
• throughput introduction
• calculating throughput

Scanner Operating
Specifications

Network Specifications

Backplane Current Consumption

600 mA @ 5V dc

Operating Temperature

+32°F to 140°F (0°C to +60°C)

Storage Temperature

-40°F to 185°F (-40°C to +85°C)

Humidity

5 to 95% without condensation

Noise Immunity

NEMA Standard ICS 2-230

Agency Certification
(when product or packaging is marked)

• CSA certified
• CSA Class I, Division 2

Groups A, B, C, D certified

• UL listed
• CE marked for all applicable

directives

Table A.1 Baud Rate Determination of Maximum Cable Length and Terminating
Resistor Size

Baud Rate

Maximum Cable
Distance (Belden 9463)

Resistor Size

Using Extended
Node Capability

57.6K baud

3048 meters (10,000 feet)

82 ohm 1/2 Watt
Brown - Green -
Brown - Gold

115.2K baud

1524 meters (5000 feet)

230.4K baud

762 meters (2500 feet)

Not Using Extended
Node Capability

57.6K baud

3048 meters (10,000 feet)

150 ohm 1/2 Watt
Brown - Green -
Brown - Gold

115.2K baud

1524 meters (5000 feet)

230.4K baud

762 meters (2500 feet)

82 ohm 1/2 Watt Gray
- Red - Black - Gold