4-34 Scanner Configuration and Programming

2. Assign the scanner to a physical slot in the SLC processor’s

chassis by selecting Scanner from the list. If the scanner
selection is not available, select OTHER from the I/O
Configuration Screen and enter the Code ID number: 13608.

3. Enter the number of Scanned Input and Output Words using the

Specialty I/O and Advanced Setup menus.

The default value is 32 I/O words. You can specify less than 32
and reduce the processor scan time by transferring only the part
of the input and output image that your application requires.

4. Using the Specialty I/O Configuration menu, set the M1 and M0

file sizes to 32 words (48 words if using complementary I/O). 32
words is the minimum required for operation. If you do not set
the M1 and M0 file sizes to at least 32 words the programming
device will not allow you to access the M files in the SLC control
program.

If you are using the block transfer (BT) function, you should set
the M1 and M0 file sizes to 3,300. Refer to Chapter 5 before
completing this selection.

5. Set the G file size to 3 (5 if using complementary I/O) using the

Specialty I/O Configuration menu.

6. Enter your setup information using the Modify G File menu.

IMPORTANT

Do not set either of these values to 0. If you
do, the scanner will not work correctly.

IMPORTANT

SLC 5/02 processors scan chassis I/O slots left
to right starting at slot 1, regardless of the
module type. SLC 5/03 and later processors
scan slots with discrete I/O modules first, left
to right starting at slot 1, and then slots with
specialty modules, left to right starting at slot 1.