Publication 1747-UM013B-EN-P - January 2005

Quick Start for Experienced Users 2-3

Make sure system power is off; then insert the scanner module
into your 1746 chassis. In this example procedure, local slot 1 is
selected.

See Chapter 3, Installation and Wiring.

5. Connect all RIO link devices.

Ensure that you:

• Daisy chain each RIO link device.
• Ground the shield drain wire to the nearest chassis mounting

bolt.

• Connect the appropriate termination resistors on each end of the

link.

6. Configure the system.

Set up your system I/O configuration for the particular slot in
which you installed the scanner (slot 1 in this example). If your
module is not listed in your software version, select Other and
enter the scanner input module ID code (13608) at the prompt
on the I/O configuration display.

See Chapter 4, Configuration and Programming.

ATTENTION

Never install, remove, or wire modules with
power applied to the chassis or devices wired
to the module.

Make sure system power is off; then insert the scanner module into your 1746 chassis.
In this example procedure, local slot 1 is selected.

Card
Guide

Top and Bottom
Module Release(s)